2.1.16. Internal Floating Point Commands (Acknowledged)
VLT
Response
Command Subcom-
mand
Re-
gion
NPA Object
no.
Attribute
No.
Attribute Message Type
Comments
ACK
1
-
5
0-101
1
Byte
Read Internal
Parameter of
object type
float
Read Object Status
associated with each
individual point
ACK
1
-
5
0-101
2
Float
Read Internal
Parameter of
object type
float
Read Current Value
attribute associated
with each individual
point
ACK
2
-
5
0-101
-
Float
Write Internal
Parameter of
object type
float
Write to Current Val-
ue attribute associ-
ated with each indi-
vidual point
ACK
2
-
5
0-101
-
Float
Write Internal
Parameter of
object type
float
Write to Current Val-
ue attribute associ-
ated with each indi-
vidual point
ACK
7
2
5
0-101
-
Float Override Inter-
nal Parameter
of object type
float
Write to internal pa-
rameter current val-
ue (set-up parame-
ters for VLT)
ACK
7
3
5
0-101
-
-
Override Re-
lease
Set the current value,
the value that it was
before the 1. Over-
ride Command was
issued
Table 2.10: No Error Code coloumn in this table.