Internal Floating Point (ADF), contin-
ued..
NPT
NPA
UNIT
DESCRIPTION
RANGE
PARAMETER
NUMBER
ADF
110
Sec
Option B Relay 1 ON Delay 0.01 to 600.00
5-41:6
ADF
111
Sec
Option B Relay 1 OFF Delay 0.01 to 600.00
5-42:6
ADF
112
Sec
Option B Relay 2 ON Delay 0.01 to 600.00
5-41:7
ADF
113
Sec
Option B Relay 2 OFF Delay 0.01 to 600.00
5-42:7
ADF
114
Sec
Option B Relay 3 ON Delay 0.01 to 600.00
5-41:8
ADF
115
Sec
Option B Relay 3 OFF Delay 0.01 to 600.00
5-42:8
ADF
120
V
Analogue Input X42/1 Low
Voltage
0.07 to 10.00
26-10
ADF
121
V
Analogue Input X42/1 High
Voltage
0.07 to 10.00
26-11
ADF
122
V
Analogue Input X42/3 Low
Voltage
0.07 to 10.00
26-20
ADF
123
V
Analogue Input X42/3 High
Voltage
0.07 to 10.00
26-21
ADF
124
V
Analogue Input X42/5 Low
Voltage
0.07 to 10.00
26-30
ADF
125
V
Analogue Input X42/6 High
Voltage
0.07 to 10.00
26-31
ADF
130
%
Analogue output X42/7
Timeout preset
0.00 to 100.00
26-53
ADF
131
%
Analogue output X42/9
Timeout preset
0.00 to 100.00
26-64
ADF
132
%
Analogue output X42/11
Timeout preset
0.00 to 100.00
26-74
ADF
140
ECB Bypass Start timer de-
lay
0-60
31-01
ADF
141
ECB Drive Trip Bypass delay 0-300
31-02
1
"Feedback" if closed loop - and "100 Hz" if open loop
2
Unit is power dependent
3
The drive must be stopped to change this point
4
The point is global in all 4 setups
5
Not availabele in all units.