2.2.3. Status Update Request
A Status Update Request will cause the drive to report its current operating status. The status
codes, descriptions and associated alarms are shown in the chart below.
The Device Status Code consists of two parts. The Least Significant Byte, (LSB) of the hex number
is the Alarm Number. The Most Significant Byte (MSB) indicates if the alarm is a normal trip (01)
that can be reset automatically or manually, or if the alarm is a trip lock (02) requiring cycling
power to the drive.
Status codes with associated alarms and
descriptions
Device Status Code1
Alarm
No.
Description
0x0000
-
Device OK
0x0102
2
Live zero error
0x0204
4
Phase fault (Trip lock)
0x0107
7
Over voltage
0x0108
8
Under voltage
0x0109
9
Inverter overloaded
0x010A
10
Motor overloaded
0x010B
11
Motor thermistor
0x010C
12
Current limit
0x020D
13
Over current (Trip lock)
0x020E
14
Earth fault (Trip lock)
0x020F
15
Switch mode fault (Trip lock)
0x0210
16
Short circuit (Trip lock)
0x0111
17
Standard bus time out
0x0112
18
HPFB time out
0x0116
22
Auto optimization not OK
0x021D
29
Heat sink temperature to high (Trip
lock)
0x011E
30
Motor phase U missing
0x011F
31
Motor phase V missing
0x0120
32
Motor phase W missing
0x0122
34
Profibus communication error
0x0225
37
Inverter fault (Trip lock)
0x013C
60
Safety interlock
0x0263
99
Unknown fault (Trip lock)
Read / Write Notes
A write command to an ADF (Internal Floating Point) or BD (Internal Byte) point type will be stored
in the drive's EEPROM.
NB!
If write command is issued to an overridden point, the new value will not be stored
in the drive's EEPROM.