3.1.4. Binary Outputs (BO)
NPT
NPA
UNIT
DESCRIPTION RANGE
1)
PARAMETER NUMBER
BO
0
-
DC brake inverse
0=Not Active
,
1=Active
CTW
BO
1
-
Coast inverse
0=Not Active
,
1=Active
CTW
BO
2
-
Stop inverse
0=Not Active
,
1=Active
CTW
BO
3
-
Freeze output in-
verse
0=Not Active
,
1=Active
CTW
BO
4
-
Start
0=Not Active
,
1=Active
CTW
BO
5
-
Reset
0=Not Active
,
1=Active
CTW
BO
6
-
Jogging
0=Not Active
,
1=Active
CTW
BO
8
-
Relay01
0=Not Active
,
1=Active
CTW
BO
9
-
Relay04
0=Not Active
,
1=Active
CTW
BO
10
-
Reversing
0=Not Active
,
1=Active
CTW
BO
11
Preset ref. LSB
CTW
BO
12
Preset ref. MSB
CTW
BO
13
Reserved
CTW
BO
14
Reserved
CTW
BO
15
Reserved
CTW
BO
20
Output Terminal
27
5-90:0
BO
21
Output Terminal
29
5-90:1
BO
22
Output Terminal
X30/6
5-90:2
BO
23
Output Terminal
X30/7
5-90:3
BO
24
CC Relay 1
5-90:4
BO
25
CC Relay 2
5-90:5
BO
26
Option B Relay 1
5-90:6
BO
27
Option B Relay 2
5-90:7
BO
28
Option B Relay 3
5-90:8
BO
29
Reserved
5-90:9
BO
30
Reserved
5-90:10
BO
31
Reserved
5-90:11
BO
32
Reserved
5-90:12
BO
33
Reserved
5-90:13
BO
34
Reserved
5-90:14
BO
35
Reserved
5-90:15
BO
36
Option C Relay 1
5-90:16
BO
37
Option C Relay 2
5-90:17
BO
38
Option C Relay 3
5-90:18
BO
39
Option C Relay 4
5-90:19
BO
40
Option C Relay 5
5-90:20
BO
41
Option C Relay 6
5-90:21
BO
42
Option C Relay 7
5-90:22
BO
43
Option C Relay 8
5-90:2
BO
44
Reserved
5-90:24
BO
45
Reserved
5-90:25
BO
46
Reserved
5-90:26
BO
47
Reserved
5-90:27
BO
48
Reserved
5-90:28
BO
49
Reserved
5-90:29
BO
50
Reserved
5-90:30
BO
51
Reserved
5-90:31
BO
52
ECB Activate
31-90
1) The values in
BOLD
are the default values.
VLT
®
HVAC Drive Metasys N2
3. Appendix
MG.11.G1.02 - VLT
®
is a registered Danfoss trademark
29