RFI Filter
Type
Conduct emission. Maximum shielded cable length [m]
Radiated emission
Industrial environment
Housing, trades and
light industries
Industrial
environment
Housing, trades and
light industries
EN 55011 Class A2
EN 55011 Class A1
EN 55011 Class B
EN 55011 Class A1
EN 55011 Class B
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
Without
external
filter
With
external
filter
30–125 hp
[22–90 kW]
3x380–480 V
IP54
25
10
Yes
No
Table 1.31 Test Results
1.7.5 General Specifications
Protection and features
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips in case of overtem-
perature.
•
The adjustable frequency drive is protected against short-circuits between motor terminals U, V, W.
•
When a motor phase is missing, the adjustable frequency drive trips and issues an alarm.
•
When a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips when the
intermediate circuit voltage is too low or too high.
•
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
Line power supply (L1, L2, L3)
Supply voltage
200–240 V
±
10%
Supply voltage
380–480 V
±
10%
Supply voltage
525–600 V
±
10%
Supply frequency
50/60 Hz
Max. temporary imbalance between line phases
3.0% of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
φ
) near unity
(>0.98)
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1-H5, I2, I3, I4
Max. 2 times/min.
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6-H8, I6-I8
Max. 1 time/min.
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/480 V
maximum.
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–200 Hz (VVC
plus
), 0–400 Hz (u/f)
Switching on output
Unlimited
Ramp times
0.05–3600 s
Quick Guide
Quick Guide
MG18A522