Adjustable frequency drive
PK75
P1K5
P2K2
P3K0
P4KO
P5K5
P7K5
P11K
P15K
P18K
Typical shaft output [kW]
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
18.5
Typical shaft output [hp]
1.0
2.0
3.0
4.0
5.0
7.5
10.0
15
20
25
IP54 frame
I2
I2
I2
I2
I2
I3
I3
I4
I4
I4
Max. cable size in terminals (line power, motor)
[mm
2
/AWG]
4/10
4/10
4/10
4/10
4/10
4/10
4/10
16/6
16/6
16/6
Output current
104 °F [40
°
C] ambient temperature
Continuous (3x380–440 V) [A]
2.2
3.7
5.3
7.2
9.0
12.0
15.5
23.0
31.0
37.0
Intermittent (3x380–440 V) [A]
2.4
4.1
5.8
7.9
9.9
13.2
17.1
25.3
34.0
40.7
Continuous (3x440–480 V) [A]
2.1
3.4
4.8
6.3
8.2
11.0
14.0
21.0
27.0
34.0
Intermittent (3x440–480 V) [A]
2.3
3.7
5.3
6.9
9.0
12.1
15.4
23.1
29.7
37.4
Max. input current
Continuous (3x380–440 V) [A]
2.1
3.5
4.7
6.3
8.3
11.2
15.1
22.1
29.9
35.2
Intermittent (3x380–440 V) [A]
2.3
3.9
5.2
6.9
9.1
12.3
16.6
24.3
32.9
38.7
Continuous (3x440–480 V) [A]
1.8
2.9
3.9
5.3
6.8
9.4
12.6
18.4
24.7
29.3
Intermittent (3 x 440–480 V) [A]
2.0
3.2
4.3
5.8
7.5
10.3
13.9
20.2
27.2
32.2
Max. electrical fuses
See
chapter 1.3.5 Fuses and Circuit Breakers
Estimated power loss [W], best case/typical
1)
21/
16
46/
57
46/
58
66/
83
95/
118
104/
131
159/
198
248/
274
353/
379
412/
456
Weight enclosure IP54 [kg]
11.69
[5.3]
11.69
[5.3]
11.69
[5.3]
11.69
[5.3]
11.69
[5.3]
15.87
[7.2]
15.87
[7.2]
30.42
[13.8]
30.42
[13.8]
30.42
[13.8]
Efficiency [%], best case/typical 1
98.0/
97.6
97.7/
97.2
98.3/
97.9
98.2/
97.8
98.0/
97.6
98.4/
98.0
98.2/
97.8
98.1/
97.9
98.0/
97.8
98.1/
97.9
Output current - +122 °F [+50
°
C] ambient temperature
Continuous (3x380–440 V) [A]
1.93
3.7
4.85
6.3
7.5
10.9
14.0
20.9
28.0
33.0
Intermittent (3x380–440 V) [A]
2.1
4.07
5.4
6.9
9.2
12.0
15.4
23.0
30.8
36.3
Continuous (3x440–480 V) [A]
1.8
3.4
4.4
5.5
6.8
10.0
12.6
19.1
24.0
30.0
Intermittent (3x440–480 V) [A]
2.0
3.7
4.8
6.1
8.3
11.0
13.9
21.0
26.4
33.0
Table 1.28 3x380-480 V AC, PK75-P18K, I2-I4
Quick Guide
Quick Guide
MG18A522
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
39
1
1