Parameter
Option
Default
Function
6-11 Terminal 53 High Voltage
0–10 V
10 V
Enter the voltage that corresponds to the
high reference value.
6-12 Terminal 53 Low Current
0–20 mA
4
Enter the current that corresponds to the low
reference value.
6-13 Terminal 53 High Current
0–20 mA
20
Enter the current that corresponds to the high
reference value.
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1
Select if terminal 53 is used for current or
voltage input.
Table 1.21 Open-loop Applications Set-up
Quick Guide
Quick Guide
26