1.7 General Specifications
1.7.1 Line Power Supply 3x200–240 V AC
Adjustable frequency
drive
PK25 PK37 PK75 P1K5 P2K2 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
Typical shaft output [kW]
0.25
0.37
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37.0
45.0
Typical shaft output [hp]
0.33
0.5
1.0
2.0
3.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
IP20 frame
H1
H1
H1
H1
H2
H3
H4
H4
H5
H6
H6
H7
H7
H8
H8
Max. cable size in
terminals (line power,
motor) [mm
2
/AWG]
4/10
4/10
4/10
4/10
4/10
4/10
16/6
16/6
16/6
35/2
35/2
50/1
50/1
95/0
120/
(4/0)
Output current
104 °F [40
°
C] ambient temperature
Continuous (3x200–240 V)
[A]
1.5
2.2
4.2
6.8
9.6
15.2
22.0
28.0
42.0
59.4
74.8
88.0
115.0 143.0 170.0
Intermittent
(3x200–240 V) [A]
1.7
2.4
4.6
7.5
10.6
16.7
24.2
30.8
46.2
65.3
82.3
96.8
126.5 157.3 187.0
Max. input current
Continuous (3x200–240 V)
[A]
1.1
1.6
2.8
5.6
8.6/
7.2
14.1/
12.0
21.0/
18.0
28.3/
24.0
41.0/
38.2
52.7
65.0
76.0
103.7 127.9 153.0
Intermittent
(3x200–240 V) [A]
1.2
1.8
3.1
6.2
9.5/
7.9
15.5/
13.2
23.1/
19.8
31.1/
26.4
45.1/
42.0
58.0
71.5
83.7
114.1 140.7 168.3
Max. electrical fuses
See
chapter 1.3.5 Fuses and Circuit Breakers
Estimated power loss [W],
Best case/typical1)
12/
14
15/
18
21/
26
48/
60
80/
102
97/
120
182/
204
229/
268
369/
386
512
697
879
1149 1390 1500
Weight enclosure IP20 lb
[kg]
4.41
[2.0]
4.41
[2.0]
4.41
[2.0]
4.63
[2.1]
7.5
[3.4]
9.92
[4.5]
17.42
[7.9]
17.42
[7.9]
20.94
[9.5]
54.01
[24.5]
54.01
[24.5]
79.37
[36.0]
79.37
[36.0]
112.
44
[51.0]
112.
44
[51.0]
Efficiency [%], best case/
typical
1)
97.0/
96.5
97.3/
96.8
98.0/
97.6
97.6/
97.0
97.1/
96.3
97.9/
97.4
97.3/
97.0
98.5/
97.1
97.2/
97.1
97.0
97.1
96.8
97.1
97.1
97.3
Output current
122 °F [50
°
C] ambient temperature
Continuous (3x200–240 V)
[A]
1.5
1.9
3.5
6.8
9.6
13.0
19.8
23.0
33.0
41.6
52.4
61.6
80.5 100.1
119
Intermittent (3x200–240
V) [A]
1.7
2.1
3.9
7.5
10.6
14.3
21.8
25.3
36.3
45.8
57.6
67.8
88.6 110.1 130.9
Table 1.25 3x200–240 V AC, PK25-P45K
1) At rated load conditions
Quick Guide
Quick Guide
36
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
MG18A522
1
1