Adjustable frequency drive
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output [kW]
22.0
30.0
37.0
45.0
55.0
75.0
90.0
Typical shaft output [hp]
30.0
40.0
50.0
60.0
70.0
100.0
125.0
IP54 frame
I6
I6
I6
I7
I7
I8
I8
Max. cable size in terminals (line power, motor)
[mm
2
/AWG]
35/2
35/2
35/2
50/1
50/1
95/(3/0)
120/(4/0)
Output current
104 °F [40
°
C] ambient temperature
Continuous (3x380–440 V) [A]
44.0
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent (3x380–440 V) [A]
48.4
67.1
80.3
99.0
116.6
161.7
194.7
Continuous (3x440–480 V) [A]
40.0
52.0
65.0
80.0
105.0
130.0
160.0
Intermittent (3x440–480 V) [A]
44.0
57.2
71.5
88.0
115.5
143.0
176.0
Max. input current
Continuous (3x380–440 V) [A]
41.8
57.0
70.3
84.2
102.9
140.3
165.6
Intermittent (3x380–440 V) [A]
46.0
62.7
77.4
92.6
113.1
154.3
182.2
Continuous (3x440–480 V) [A]
36.0
49.2
60.6
72.5
88.6
120.9
142.7
Intermittent (3 x 440–480 V) [A]
39.6
54.1
66.7
79.8
97.5
132.9
157.0
Max. electrical fuses
Estimated power loss [W], best case/typical
1)
496
734
995
840
1099
1520
1781
Weight enclosure IP54 [kg]
59.53 [27] 59.53 [27] 59.53 [27] 99.21 [45]
99.21
[45]
143.3 [65] 143.3 [65]
Efficiency [%], best case/Typical 1
98.0
97.8
97.6
98.3
98.2
98.1
98.3
Output current - +122 °F [+50
°
C] ambient temperature
Continuous (3x380–440 V) [A]
35.2
48.8
58.4
63.0
74.2
102.9
123.9
Intermittent (3x380–440 V) [A]
38.7
53.9
64.2
69.3
81.6
113.2
136.3
Continuous (3x440–480 V) [A]
32.0
41.6
52.0
56.0
73.5
91.0
112.0
Intermittent (3x440–480 V) [A]
35.2
45.8
57.2
61.6
80.9
100.1
123.2
Table 1.29 3x380–480 V AC, P11K-P90K, I6-I8
Quick Guide
Quick Guide
40
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
MG18A522
1
1