Parameter
Range
Default
Function
20-94 PI Integral Time
0.1–999.0 s
999.0 s
Enter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
Table 1.22 Closed-loop Set-up
Motor set-up
The Quick Menu Motor Set-up guides you through the needed motor parameters.
Parameter
Range
Default
Function
0-03 Regional Settings
[0] International
[1] US
0
0-06 GridType
[0] -[132] see start-up wizard for
open-loop application
Size selected
Select operating mode for restart
upon reconnection of the drive to AC
line voltage after power-down
1-10 Motor Construction
*[0] Motor construction
[1] PM, non-salient SPM
[0] Asynchron
1-20 Motor Power
0.12–110 kW/0.16–150 hp
Size related
Enter motor power from nameplate
data
1-22 Motor Voltage
50.0–1000.0 V
Size related
Enter motor voltage from nameplate
data
1-23 Motor Frequency
20.0–400.0 Hz
Size related
Enter motor frequency from
nameplate data
1-24 Motor Current
0.01–10000.00 A
Size related
Enter motor current from nameplate
data
1-25 Motor Nominal Speed
100.0–9,999.0 RPM
Size related
Enter motor nominal speed from
nameplate data
1-26 Motor Cont. Rated Torque 0.1–1000.0
Size related
This parameter is available only when
1-10 Motor Construction Design is set
to
[1] PM, non-salient SPM
.
NOTICE!
Changing this parameter affects
the settings of other parameters
1-30 Stator Resistance (Rs)
0.000–99.990
Size related
Set the stator resistance value
1-37 d-axis Inductance (Ld)
0–1000
Size related
Enter the value of the d-axis
inductance.
Obtain the value from the permanent
magnet motor data sheet. The de-axis
inductance cannot be found by
performing an AMA.
1-39 Motor Poles
2–100
4
Enter the number of motor poles
1-40 Back EMF at 1000 RPM
10–9000
Size related
Line-Line RMS back EMF voltage at
1000 RPM
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select Enable to enable the adjustable
frequency drive to catch a spinning
motor.
3-41 Ramp 1 Ramp Up Time
0.05–3600.0 s
Size related
Ramp-up time from 0 to rated
1-23 Motor Frequency
Quick Guide
Quick Guide
30
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
MG18A522