VLT
®
FCD Series
■
Factory Settings
PNU
#
Parameter
description
Factory setting
Changes
during
operation
4-setup
Conv.
index
Data
type
200
Output frequency range
Clockwise only, 0-132
Hz
No
Yes
0
5
201
Output frequency,
low limit f
MIN
0.0 Hz
Yes
Yes
-1
6
202
Output frequency,
high limit f
MAX
132 Hz
Yes
Yes
-1
6
203
Reference range
Min ref.-Max ref.
Yes
Yes
0
5
204
Minimum ref Ref
MIN
0.000 Hz
Yes
Yes
-3
4
205
Maximum ref Ref
MAX
50.000 Hz
Yes
Yes
-3
4
206
Ramp type
Linear
Yes
Yes
0
5
207
Ramp-up time 1
3.00 sec.
Yes
Yes
-2
7
208
Ramp-down time 1
3.00 sec.
Yes
Yes
-2
7
209
Ramp-up time 2
3.00 sec.
Yes
Yes
-2
7
210
Ramp-down time 2
3.00 sec.
Yes
Yes
-2
7
211
Jog ramp time
3.00 sec.
Yes
Yes
-2
7
212
Quick stop ramp-down time
3.00 sec.
Yes
Yes
-2
7
213
Jog frequency
10.0 Hz
Yes
Yes
-1
6
214
Reference function
Sum
Yes
Yes
0
5
215
Preset reference 1
0.00%
Yes
Yes
-2
3
216
Preset reference 2
0.00%
Yes
Yes
-2
3
217
Preset reference 3
0.00%
Yes
Yes
-2
3
218
Preset reference 4
0.00%
Yes
Yes
-2
3
219
Catch up/slow down
reference
0.00%
Yes
Yes
-2
6
221
Current limit
160 %
Yes
Yes
-1
6
223
Warn. Low current
0.0 A
Yes
Yes
-1
6
224
Warn. High current
I
MAX
Yes
Yes
-1
6
225
Warn. Low frequency
0.0 Hz
Yes
Yes
-1
6
226
Warn. High frequency
132.0 Hz
Yes
Yes
-1
6
227
Warn. Low Feedback
-4000.000
Yes
Yes
-3
4
228
Warn. High Feedback
4000.000
Yes
Yes
-3
4
229
Frequency bypass,
bandwidth
0 Hz (OFF)
Yes
Yes
0
6
230
Frequency bypass 1
0.0 Hz
Yes
Yes
-1
6
231
Frequency bypass 2
0.0 Hz
Yes
Yes
-1
6
MG.04.B7.02 - VLT is a registered Danfoss trademark