VLT
®
FCD Series
All about FCD
300
Safeguards:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the power module ensures that the frequency converter cuts
out if the temperature reaches 100 °C. An overload temperature cannot be reset until the
temperature of the power module is below 70 °C.
•
The frequency converter is protected against short-circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter will cut out.
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if
the intermediate circuit voltage is too low or too high.
•
The frequency converter is protected against earth fault on motor terminals U, V, W.
MG.04.B7.02 - VLT is a registered Danfoss trademark