ALARM 56: AMT warning during AMT
A frequency converter warning is given while
AMT is being performed.
WARNING 99: Locked
See parameter 18.
■
Warning words, extended status words
and alarm words
Warning words, status words and alarm words
appear in the display in Hex format. If there are
several warnings, status words or alarms, a total
of all the warnings, status words or alarms will be
displayed. Warning words, status words and alarm
words can also be read out using the serial bus in
parameters 540, 541 and 538 respectively.
Bit (Hex)
Warning words
000008
HPFB bus timeout
000010
Standard bus timeout
000040
Current limit
000080
Motor thermistor
000100
Motor overload
000200
Inverter overload
000400
Undervolt
000800
Overvolt
001000
Voltage warning low
002000
Voltage warning high
004000
Phase loss
010000
Live zero error
400000
Out of frequency range
800000
Profibus communication fault
40000000
Switch mode warning
80000000
Heat sink temperature high
Bit (Hex)
Extended status words
000001
Ramping
000002
AMT running
000004
Start forw./reverse
000008
Slow down
000010
Catch-up
000020
Feedback high
000040
Feedback low
000080
Output current high
000100
Output current low
000200
Output frequency high
000400
Output frequency low
002000
Braking
008000
Out of frequency range
Bit (Hex)
Alarm words
000002
Triplock
000004
AMT tuning fail
000040
HPFP bus timeout
000080
Standard bus timeout
000100
Curr. short circuit
000200
Switch mode fault
000400
Earth fault
000800
Overcurrent
002000
Motor thermistor
004000
Motor overload
008000
Inverter overload
010000
Undervolt
020000
Overvolt
040000
Phase loss
080000
Live zero error
100000
Heat sink temperature too high
2000000
Profibus communication fault
8000000
Inrush fault
10000000
Internal fault
■
Spare parts
The complete electronic part can be used as a
spare part. The following four parts can replace all
FCD 303-330 with and without Profibus.
For servicing DeviceNet and AS-interface units
an additional control card is required to upgrade
the electronic spare part.
FCD 303 178B1484
FCD 307 178B1485
FCD 315 178B1486
FCD 330 178B2301
The parts can be downsized one size simply
by selecting the correct motor size, and the
Profibus functionality can be changed/eliminated
in Parameter 678.
The control card can also be replaced for
repair of the electronic part.
Profibus, 12 MB control card 175N2338
DeviceNet control card 175N2325
AS-interface control card 175N2324
For servicing the installation box a kit containing
various parts, plugs, and terminal PCB can
be ordered 175N2121.
Service tool kit 175N2404
It is normally not possible to operate the FCD300 with
open lid. Using the service tool kit, the electronic part
and the installation box can be connected without
joining them. This might be helpful if measurements
on input/output terminals are required during servicing.