VLT
®
FCD Series
■
Technical functions
600-605 Operating Data
Value:
Par. no.
Description
Display text
Unit
Range
600
Operating hours
(OPERATING HOURS)
Hours
0-130,000.0
601
Hours run
(RUNNING HOURS)
Hours
0-130,000.0
602
kWh counter
(KWH COUNTER)
kWh
Depends on unit
603
Number of power-up
’
s
(POWER UP
’
S)
Number of times
0-9999
604
Number of overtemperatures
(OVER TEMP
’
S)
Number of times
0-9999
605
Number of overvoltages
(OVER VOLT
’
S)
Number of times
0-9999
Function:
These parameters can be read out via the serial
communication port and the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the frequency
converter has been operating. The value is
saved every hour and when there is a mains
failure. This value cannot be reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been
operating since the reset in parameter 619
Reset
of hours-run counter
. The value is saved every
hour and when there is a mains failure.
Parameter 602, kWh counter:
Gives the frequency converter
’
s output energy in
kWh. The calculation is based on the mean kW
value over one hour. This value can be reset using
parameter 618
Reset of kWh counter
.
Range: 0 - depends on unit.
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage
undertaken on the frequency converter.
Parameter 604, Number of overtemperatures:
Gives the number of overtemperature faults that have
been registered on the frequency converter
’
s heat sink.
Parameter 605, Number of overvoltages:
Gives the number of overvoltages of the intermediate
circuit voltage in the frequency converter. This is only
counted when Alarm 7
Overvoltage
is active.
NB!:
Parameters 615-617
Fault log
cannot be read
out via the integral control unit.
615 Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason for
a trip (cut-out of the frequency converter) occurring.
10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most
recently saved data value. The highest log number
[10] contains the oldest data value saved. If a trip
occurs, it is possible to see the cause, time and a
possible value of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a
table. See the table in
Warnings/alarm messages
.
616 Fault log: Time
(F.LOG: TIME)
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter it is possible to see the total number
of operating hours in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest
log number [1] contains the latest/most recently
saved data value, and the highest log number
[10] contains the oldest data value.
Description of choice:
Read out as one value.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
96