+24V
RS485
18
37
130BD007.10
1
3
4
6
2
5
Illustration 6.3 Analog Inputs
Item
Description
1
Functional isolation
2
Control
3
PELV isolation
4
Mains
5
High voltage
6
Motor
Table 6.5 Legend
Pulse/encoder inputs
Programmable pulse/encoder inputs
2/1
Terminal number pulse/encoder
29, 33
1)
/32
2)
, 33
2)
Max. frequency at terminal 29, 32, 33
110 kHz (Push-pull driven)
Max. frequency at terminal 29, 32, 33
5 kHz (open collector)
Min. frequency at terminal 29, 32, 33
4 Hz
Voltage level
see
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
Pulse input accuracy (0.1 to 1 kHz)
Max. error: 0.1% of full scale
Encoder input accuracy (1 to 110 kHz)
Max. error: 0.05% of full scale
The pulse and encoder inputs (terminals 29, 32, 33) are galvanically isolated from the supply voltage (PELV) and other high-
voltage terminals.
1)
Pulse inputs are 29 and 33
2)
Encoder inputs: 32=A, and 33=B
Analog output
Number of programmable analog outputs
1
Terminal number
42
Current range at analog output
0/4 to 20 mA
Max. load GND - analog output less than
500
Ω
Accuracy on analog output
Max. error: 0.5% of full scale
Resolution on analog output
12 bit
The analogue output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS-485 serial communication
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs
2
Terminal number
27, 29
1)
Voltage level at digital/frequency output
0-24 V
Max. output current (sink or source)
40 mA
Max. load at frequency output
1 k
Ω
Max. capacitive load at frequency output
10 nF
Minimum output frequency at frequency output
0 Hz
Maximum output frequency at frequency output
32 kHz
Accuracy of frequency output
Max. error: 0.1% of full scale
Specifications
VLT
®
Decentral Drive FCD 302
86
MG04H102 - VLT
®
is a registered Danfoss trademark
6
6