130BC384.10
3 phase
power
input
Mechanical
brake
+10Vdc
-10Vdc-
+10Vdc
0/4-20 mA
-10Vdc-
+10Vdc
0/4-20 mA
91 (L1)
92 (L2)
93 (L3)
95 (PE)
122(MBR+)
123(MBR-)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN/OUT)
29 (D IN/OUT)
24V
OV
32 (D IN)
33 (D IN)
37 (D IN)
S201
S202
ON/I=0-20mA
OFF/U=0-10V
P 5-00
24V (NPN)
OV (PNP)
24V (NPN)
OV (PNP)
24V (NPN)
OV (PNP)
24V (NPN)
OV (PNP)
24V (NPN)
OV (PNP)
24V (NPN)
OV (PNP)
Switch Mode
Power Supply
10Vdc
15mA
24Vdc
600mA
(U) 96
(U) 97
(W) 98
(PE) 99
Motor
Brake
resistor
(R+) 82
(R-) 81
relay1
relay2
03
02
01
06
05
04
240Vac, 2A
240Vac, 2A
400Vac, 2A
Analog Output
0/4-20 mA
(COM A OUT) 39
(A OT) 42
ON=Terminated
OFF=Open
S801
S801
GX
(N RS-485) 69
(P RS-485) 68
5V
RS-485
Interface
(COM RS-485) 61
(PNP) = Source
(NPN) = Sink
RS-485
ON
1 2
ON
1 2
ON
1 2
0V
VCXA
Profibus
interface
GND1
GND1
RS485
66
63
62
67
GX
Illustration 3.14 Electrical Terminals without Options
A=analog, D=digital
Terminal 37 is used for Safe Stop.
Relay 2 has no function when the frequency converter has
mechanical brake output.
Very long control cables and analogue signals may in rare
cases result in 50/60 Hz earth loops due to noise from
mains supply cables. If this occurs, it may be necessary to
break the screen or insert a 100 nF capacitor between
screen and chassis. Connect the digital and analogue
inputs and outputs separately to the common inputs
(terminal 20, 55, 39) to avoid ground currents from both
groups affecting other groups. For example, switching on
the digital input may disturb the analog input signal.
System Integration
VLT
®
Decentral Drive FCD 302
MG04H102 - VLT
®
is a registered Danfoss trademark
37
3
3