9.1.3 Mains Supply 3x380-480 V AC
Normal overload 150% for 1 min
Frequency converter
Typical Shaft Output [kW]
PK37
0.37
PK75
0.75
P1K5
1.5
P2K2
2.2
P3K0
3.0
P4K0
4.0
Typical Shaft Output [HP]
0.5
1
2
3
4
5
IP 20
Frame
M1
Frame
M1
Frame
M2
Frame
M2
Frame
M3
Frame
M3
Output current
Continuous (3x380-440 V) [A]
1.2
2.2
3.7
5.3
7.2
9.0
Intermittent (3x380-440 V) [A]
1.8
3.3
5.6
8.0
10.8
13.7
Continuous (3x440-480 V) [A]
1.1
2.1
3.4
4.8
6.3
8.2
Intermittent (3x440-480 V) [A]
1.7
3.2
5.1
7.2
9.5
12.3
Max. cable size:
(mains, motor) [mm
2
/ AWG]
4/10
Max. input current
Continuous (3x380-440 V) [A]
1.9
3.5
5.9
8.5
11.5
14.4
Intermittent (3x380-440 V) [A]
2.6
4.7
8.7
12.6
16.8
20.2
Continuous (3x440-480 V) [A]
1.7
3.0
5.1
7.3
9.9
12.4
Intermittent (3x440-480 V) [A]
2.3
4.0
7.5
10.8
14.4
17.5
Max. mains fuses [A]
See
Environment
Estimated power loss [W], Best case/
Typical
1)
18.5/
25.5
28.5/
43.5
41.5/
56.5
57.5/
81.5
75.0/
101.6
98.5/
133.5
Weight enclosure IP20 [kg]
1.1
1.1
1.6
1.6
3.0
3.0
Efficiency [%], Best case/Typical
1)
96.8/
95.5
97.4/
96.0
98.0/
97.2
97.9/
97.1
98.0/
97.2
98.0/
97.3
Table 9.3 Mains Supply 3x380-480 V AC
1)
At rated load conditions.
Specifications
VLT
®
Micro Drive FC 51 Design Guide
84
MG02K302 - Rev. 2013-12-03
9
9