The PC-based Configuration Tool MCT 10 Set-up
Software modules
The following modules are included in the software
package:
MCT 10 Set-up Software
Setting parameters
Copy to and from frequency converters
Documentation and print out of parameter
settings incl. diagrams
Ext. User Interface
Preventive Maintenance Schedule
Clock settings
Timed Action Programming
Smart Logic Controller Set-up
Table 6.9 MCT 10 Set-up Software
Ordering number:
Order the CD containing the PC-based Configuration Tool
MCT 10 Set-up Software using code number 130B1000.
MCT 10 Set-up Software can also be downloaded from the
Danfoss Internet:
www.danfoss.com/BusinessAreas/DrivesSo-
lutions/Softwaredownload/DDPC+SProgram.htm
.
6.20 Safety
6.20.1 High Voltage Test
Carry out a high voltage test by short-circuiting terminals
U, V, W, L
1
, L
2
and L
3
. Energise maximum 2.15 kV DC for
380-500 V frequency converters and 2.525 kV DC for
525-690 V frequency converters for 1 s between this short-
circuit and the chassis.
WARNING
When running high voltage tests of the entire instal-
lation, interrupt the mains and motor connection if the
leakage currents are too high.
Failure to follow recommendations could result in death
or serious injury.
6.20.2 Safety Earth Connection
The frequency converter has a high leakage current and
must be grounded appropriately for safety reasons
according to EN 50178.
WARNING
The ground leakage current from the frequency
converter exceeds 3.5 mA. To ensure a good mechanical
connection from the earth cable to the earth connection
(terminal 95), the cable cross-section must be at least 10
mm
2
or 2 rated ground wires terminated separately.
How to Install
VLT
®
Micro Drive FC 51 Design Guide
MG02K302 - Rev. 2013-12-03
57