4.1.14 FC 51 DIN Rail Kit Mounting
Instruction
Step 1
Mount plastic part on frequency converter.
Illustration 4.27 Mount Plastic Part
Step 2
Fit frequency converter on DIN rail (Din Rail kit is only for
M1 and M2).
Illustration 4.28 Fit Frequency Converter on DIN Rail
4.1.15 Line Filter MCC 107 Installation
Instructions
Line filters of the type MCC 107 combine a harmonic filter
and an EMC filter. The line filters improve performance of
the line current to the frequency converter. The 3 different
line filter frame sizes correspond to the VLT
®
Micro Drive
enclosure types M1, M2 and M3.
4
130BC160.10
2
3
1
1 Mounting holes for frequency converter
2 Input terminal
3 Output line
4 Protective earth (PE)
Illustration 4.29 Line Filter MCC 107 with Micro Drive FC 51
CAUTION
Hot surfaces
Risk of high surface temperatures.
•
Do NOT touch the line filter during operation or
wear protective gloves
WARNING
High voltage
Risk of electric shock.
•
Never carry out maintenance work on the line
filter during operation. Wait at least 4 minutes
after the equipment has been disconnected
from the frequency converter before touching
any potentially live parts.
NOTICE
•
Never repair a defective filter
Selection
VLT
®
Micro Drive FC 51 Design Guide
34
MG02K302 - Rev. 2013-12-03
4
4