7.8 Initialise the Frequency Converter to
Default Settings in two Ways
Recommended initialisation (via
14-22 Operation Mode
)
1.
Select
14-22 Operation Mode
.
2.
Press [OK].
3.
Select
Initialisation
and Press [OK].
4.
Cut off the mains supply and wait until the
display turns off.
5.
Reconnect the mains supply - the frequency
converter is now reset.
Except the following
parameters.
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-33 Parity / Stop Bits
8-35 Minimum Response Delay
8-36 Maximum Response Delay
15-00 Operating hours to
15-05 Over Volt's
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-30 Alarm Log: Error Code
15-4* Drive Identification parameters
2 finger initialisation:
1.
Power off the frequency converter.
2.
Press [OK] and [Menu].
3.
Power up the frequency converter while still
pressing the keys above for 10 s 2 finger initiali-
sation
4.
The frequency converter is now reset, except the
following parameters:
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-4* Drive identification parameters
Initialisation of parameters is confirmed by AL80 in the
display after the power cycle.
Programming
VLT
®
Micro Drive FC 51 Design Guide
64
MG02K302 - Rev. 2013-12-03
7
7