6.14.2 Connecting to Control Terminals
shows all control terminals of the frequency
converter. Applying Start (terminal 18) and an analog
reference (terminals 53 or 60) make the frequency
converter run.
Illustration 6.14 Overview of Control Terminals in PNP-configu-
ration and Factory Setting.
6.15 Switches
NOTICE
Do not operate switches with power on the frequency
converter.
Bus termination
Switch
BUS TER
position ON terminates the RS-485 port,
terminals 68, 69. See
Default setting = Off
Illustration 6.15 S640 Bus Termination
S200 Switches 1-4
Switch 1
*Off=PNP terminals 29
On=NPN terminals 29
Switch 2
*Off=PNP terminal 18, 19, 27 and 33
On=NPN terminal 18, 19, 27 and 33
Switch 3
No function
Switch 4
*Off=Terminal 53 0-10 V
On=Terminal 53 0/4-20 mA
*=default setting
Illustration 6.16 S200 Switches 1-4
NOTICE
Parameter 6-19 Terminal 53 Mode
must be set according
to Switch 4 position.
6.16 Final Set-Up and Test
To test the set-up and ensure that the frequency converter
is running, follow these steps.
Step 1. Locate the motor name plate
The motor is either star- (Y) or delta-connected (
Δ
). This
information is located on the motor name plate data.
Step 2. Enter the motor name plate data in this
parameter list
To access this list first press the [Quick Menu] key then
select
Q2 Quick Setup
.
1.
Motor Power [kW]
or Motor Power [HP]
1-20 Motor Power [kW]
1-21 Motor Power [HP]
2.
Motor Voltage
1-22 Motor Voltage
3.
Motor Frequency
1-23 Motor Frequency
4.
Motor Current
1-24 Motor Current
5.
Motor Nominal Speed
1-25 Motor Nominal
Speed
Table 6.4 Parameters for Quick Setup
How to Install
VLT
®
Micro Drive FC 51 Design Guide
MG02K302 - Rev. 2013-12-03
53
6