415 V
IEC
1)
480 V
UL
2)
600 V
UL
2)
690 V
IEC
1)
D6h frame
100,000 A 100,000 A
100,000 A 100,000 A
D8h frame (not
including the
N315T4)
100,000 A 100,000 A
100,000 A 100,000 A
D8h frame
(N315T4 only)
100,000 A Consult
factory
Not applicable
Table 10.9
1)
With a Bussmann type LPJ-SP or Gould Shawmut type AJT fuse.
450 A max fuse size for D6h and 900 A max fuse size for D8h.
2)
Must use Class J or L branch fuses for UL approval. 450 A max fuse
size for D6h and 600 A max fuse size for D8h.
10.3.4 Connection Tightening Torques
When tightening all electrical connections, it is very
important to tighten with the correct torque. Too low or
too high torque results in a bad electrical connection. Use
a torque wrench to ensure correct torque. Always use a
torque wrench to tighten the bolts.
Frame Size
Terminal
Torque
Bolt size
D1h/D3h/D5h/
D6h
Line power
Motor
Load sharing
Regen
19–40 Nm
(168–354 in-
lbs)
M10
Ground
Brake
8.5–20.5 Nm
(75–181 in-lbs)
M8
D2h/D4h/D7h/
D8h
Line power
Motor
Regen
Load sharing
Ground
19–40 Nm
(168–354 in-
lbs)
M10
Brake
8.5–20.5 Nm
(75–181 in-lbs)
M8
Table 10.10 Torque for Terminals
Specifications