QStop
The motor is decelerating using
3-81 Quick
Stop Ramp Time
.
•
Quick stop inverse
was chosen as a function
for a digital input (parameter group
5-1*
Digital Inputs
). The corresponding terminal
is not active.
•
The quick stop function was activated via
serial communication
Ramping
The motor is accelerating/decelerating using
the active ramp-up/down. The reference, a
limit value or a standstill is not yet reached.
Ref. high
The sum of all active references is above the
reference limit set in
4-55 Warning Reference
High
.
Ref. low
The sum of all active references is below the
reference limit set in
4-54 Warning Reference
Low
.
Run on ref.
The adjustable frequency drive is running in
the reference range. The feedback value
matches the setpoint value.
Run request
A start command has been given, but the
motor is stopped until a run permissive signal
is received via digital input.
Running
The motor is driven by the adjustable
frequency drive.
Speed high
Motor speed is above the value set in
4-53 Warning Speed High
.
Speed low
Motor speed is below the value set in
4-52 Warning Speed Low
.
Standby
In Auto On Auto mode, the adjustable
frequency drive will start the motor with a
start signal from a digital input or serial
communication.
Start delay
In
1-71 Start Delay
, a delay starting time was
set. A start command is activated and the
motor will start after the start delay time
expires.
Start fwd/rev
Start forward and start reverse were selected
as functions for two different digital inputs
(parameter group
5-1* Digital Inputs
). The
motor will start in forward or reverse
depending on which corresponding terminal
is activated.
Stop
The adjustable frequency drive has received a
stop command from the LCP, digital input or
serial communication.
Trip
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
adjustable frequency drive can be reset
manually by pressing [Reset] or remotely by
control terminals or serial communication.
Trip lock
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the adjustable frequency
drive. The adjustable frequency drive can then
be reset manually by pressing [Reset] or
remotely by control terminals or serial
communication.
Table 7.3 Operation Status
Status Messages
VLT
®
HVAC Drive D-Frame
Instruction Manual
MG16D222 - VLT
®
is a registered Danfoss trademark
7-3