Byte
Bit
Function
Details
45
0–7
Reserved
–
Table 7.2 Structures Used for Querying the Status of the Soft Starter
1) For models MCD5-0053B and smaller, this value is 10 times greater than the value shown on the LCP.
2) Product type code: 4=MCD 200, 5=MCD 500.
3) Reading bytes 14–15 (changed parameter value) reset byte 12 (changed parameter number) and bit 0 of byte 17 (parameters have changed).
Always read bytes 12 and 17 before reading bytes 14–15.
4) Bits 2–7 of byte 17 report the soft starter’s trip or warning code. If the value of bits 0–4 of byte 16 is 6, the soft starter has tripped. If bit 5=1, a
warning has activated and the soft starter continues operation.
5) Powerscale functions as follows:
0 = Multiply power by 10 to get W.
1 = Multiply power by 100 to get W.
2 = Power is shown in kW.
3 = Multiply power by 10 to get kW.
7.4 Soft Starter Internal Register Address
Internal registers within the soft starter have the functions listed in
Table 7.3
. These registers are not directly accessible via
fieldbus.
Register Description
Bits
Details
0
Version
0–5
Binary protocol version number.
6–8
Product parameter list version.
9–15
Product type code.
1)
1
Device details
–
–
2
2)
Changed parameter number
0–7
0 = No parameters have changed.
1~255 = Index number of the last parameter changed.
8–15
Total number of parameters available in the soft starter.
3
2)
Changed parameter value
0–13
Value of the last parameter that was changed, as indicated in register 2.
14–15 Reserved.
4
Soft starter state
0–4
0 = Reserved.
1 = Ready.
2 = Starting.
3 = Running.
4 = Stopping.
5 = Not ready (restart delay, restart temperature check).
6 = Tripped.
7 = Programming mode.
8 = Jog forward.
9 = Jog reverse.
5
1 = Warning.
6
0 = Warning.
1 = Initialized.
7
0 = Local control.
1 = Remote control.
8
0 = Parameters have changed.
1 = No parameters have changed.
2)
9
0 = Negative phase sequence.
1 = Positive phase sequence.
10–15 See trip codes in
Table 7.4
.
3)
5
Current
0–13
Average rms current across all 3 phases.
4)
14–15 Reserved.
6
Current
0–9
Current (% motor FLC).
10–15 Reserved.
Packet Structures
EtherNet/IP Module
16
Danfoss A/S © 05/2017 All rights reserved.
MG17M202
7
7