6 Operation
The EtherNet/IP Module is designed for use in a system
complying with the ODVA Common Industrial Protocol. For
successful operation, the scanner must also support all
functions and interfaces described in this manual.
6.1 Device Classification
The EtherNet/IP Module is an Adapter class device and
must be managed by a Scanner class device over Ethernet.
6.2 Scanner Configuration
6.2.1 EDS File
Download the EDS file from
drives.danfoss.com/services/pc-
tools
. The EDS file contains all required attributes of the
EtherNet/IP Module.
Once the EDS file is loaded, define the individual
EtherNet/IP Module. Input/output registers must be 240
bytes in size and type INT.
177HA660.10
Illustration 6.1 Module Definition of the EtherNet/IP Module,
Using RSLogix 5000
6.3 LEDs
LED name LED status Description
1
2
TX/
RX 2
TX/
RX 1
Link 2
Link 1
Error
Sta
tus
Pow
er
177HA627.10
Power
Off
The module is not powered up.
On
The module receives power.
Error
Off
The module is not powered up or does not have an IP address.
Flashing
Connection timeout.
On
Duplicate IP address.
Status
Off
The module is not powered up or does not have an IP address.
Flashing
The module has obtained an IP address but has not established any network
connections.
On
Communication has been established.
Link x
Off
No network connection.
On
Connected to a network.
TX/RX x
Flashing
Transmitting or receiving data.
Table 6.1 Feedback LEDs
Operation
EtherNet/IP Module
12
Danfoss A/S © 05/2017 All rights reserved.
MG17M202
6
6