7.3 Status Commands (Read Only)
NOTICE
Some soft starters do not support all functions.
Byte
Bit
Function
Details
0
0
Trip
1 = Tripped.
1
Warning
1 = Warning.
2
Running
0 = Unknown, not ready, ready to start, or tripped.
1 = Starting, running, stopping, or jogging.
3
Reserved
–
4
Ready
0 = Start or stop command not acceptable.
1 = Start or stop command acceptable.
5
Control from net
1 = Always, except in program mode.
6
Local/Remote
0 = Local control.
1 = Remote control.
7
At reference
1 = Running (full voltage at the motor).
1
0–7
Status
0 = Unknown (menu open).
2 = Soft starter not ready (restart delay or thermal delay).
3 = Ready to start (including warning state).
4 = Starting or running.
5 = Soft stopping.
7 = Trip.
8 = Jog forward.
9 = Jog reverse.
2–3
0–15
Trip/warning code
See trip codes in
Table 7.4
.
4
1)
0–7
Motor current (low byte)
Current (A).
5
1)
0–7
Motor current (high byte)
6
0–7
Motor 1 temperature
Motor 1 thermal model (%).
7
0–7
Motor 2 temperature
Motor 2 thermal model (%).
8–9
0–5
Reserved
–
6–8
Product parameter list version
–
9–15
Product type code
2)
–
10
0–7
Reserved
–
11
0–7
Reserved
–
12
3)
0–7
Changed parameter number
0 = No parameters have changed.
1~255 = Index number of the last parameter changed.
13
0–7
Parameters
Total numbers of parameters available in the soft starter.
14–15
0–13
Changed parameter value
3)
Value of the last parameter that was changed, as indicated in byte 12.
14–15 Reserved
–
Packet Structures
EtherNet/IP Module
14
Danfoss A/S © 05/2017 All rights reserved.
MG17M202
7
7