Byte
Bit
Function
Details
16
0–4
Soft starter state
0 = Reserved.
1 = Ready.
2 = Starting.
3 = Running.
4 = Stopping.
5 = Not ready (restart delay, restart temperature check).
6 = Tripped.
7 = Programming mode.
8 = Jog forward.
9 = Jog reverse.
5
Warning
1 = Warning.
6
Initialized
0 = Uninitialized.
1 = Initialized.
7
Local control
0 = Local control.
1 = Remote control.
17
0
Parameters
0 = Parameters have changed since last parameter read.
1 = No parameters have changed.
1
Phase sequence
0 = Negative phase sequence.
1 = Positive phase sequence.
2–7
Trip code
4)
See trip codes in
Table 7.4
.
18–19
0–13
Current
Average rms current across all 3 phases.
14–15 Reserved
–
20–21
0–13
Current (% motor FLC)
–
14–15 Reserved
–
22
0–7
Motor 1 thermal model (%)
–
23
0–7
Motor 2 thermal model (%)
–
24–25
5)
0–11
Power
–
12–13 Power scale
–
14–15 Reserved
–
26
0–7
% power factor
100% = power factor of 1.
27
0–7
Reserved
–
28
0–7
Reserved
–
29
0–7
Reserved
–
30–31
0–13
Phase 1 current (rms)
–
14–15 Reserved
–
32–33
0–13
Phase 2 current (rms)
–
14–15 Reserved
–
34–35
0–13
Phase 3 current (rms)
–
14–15 Reserved
–
36
0–7
Reserved
–
37
0–7
Reserved
–
38
0–7
Reserved
–
39
0–7
Reserved
–
40
0–7
Reserved
–
41
0–7
Reserved
–
42
0–7
Parameter list minor revision
–
43
0–7
Parameter list major revision
–
44
0–3
Digital input state
For all inputs, 0 = open, 1 = closed.
0 = Start.
1 = Stop.
2 = Reset.
3 = Input A
4–7
Reserved
–
Packet Structures