VLT® Relay Card MCB 105

Makes it possible to extend relay functions with 

3  additional relay outputs.  

„

 Max. switch rate at rated  

load/min. load  ...............................6 min

-1

/20 sec

-1

„

 Protects control cable connection

„

 Spring-loaded control wire connection

Max. terminal load:

„

 AC-1 Resistive load  ........................... 240 V  AC 2 A

„

 AC-15 Inductive  

load @cos phi 0.4  ...........................240 V AC 0.2 A

„

 DC-1 Resistive load  ..............................24 V DC 1 A

„

 DC-13 Inductive  

load @cos phi 0.4  ............................. 24 V DC 0.1 A

Min. terminal load:

„

 DC 5 V .......................................................................10 mA

Ordering number 

130B1110 standard

130B1210 coated 

(Class 3C3/IEC 60721-3-3)

VLT® Safe PLC I/O MCB 108

The VLT® AutomationDrive FC 302 provides a 

safety input based on a single-pole 24 V DC 

input.

„

 For the majority of applications, this input 

enables the user to implement safety in a 

cost-effective way. For applications that 

work with more advanced products like 

Safety PLC and light curtains, the Safe PLC 

interface enables the connection of a two-

wire safety link

„

 The Safe PLC Interface allows the Safe PLC 

to interrupt on the plus or the minus link 

without interfering the sense signal of the 

Safe PLC

Ordering number 

130B1120 standard

130B1220 coated 

(Class 3C3/IEC 60721-3-3)

VLT® Analog I/O Option  

MCB 109

This analog input/output option is easily fitted 

in the AC drive for upgrading to advanced 

performance and control using the additional 

I/O. This option also upgrades the AC drive with 

a battery back-up supply for the AC drive built-

in clock. This provides stable use of all AC drive 

clock functions as timed actions.

„

 3 analog inputs, each configurable as both 

voltage and temperature input

„

 Connection of 0-10 V analog signals as well 

as Pt1000 and Ni1000 temperature inputs

„

 3 analog outputs each configurable as 0-10 

V outputs

„

 Back-up supply for the standard clock func-

tion in the AC drive

The back-up battery typically lasts for 10 years, 

depending on environment.

Ordering number

130B1143 standard

130B1243 coated 

(Class 3C3/IEC 60721-3-3)

 

VLT® Safety Option MCB 152

The VLT® Safety Option MCB 152 enables activa-

tion of Safe Torque Off (STO) via the PROFIsafe 

fieldbus in combination with VLT® PROFINET 

MCA 120 fieldbus option. It improves flexibility 

by connecting safety devices within a plant.

The safety functions of the MCB 152 are 

implemented according to EN IEC 61800-5-2. 

The MCB 152 supports PROFIsafe functionality 

to activate integrated safety functions of the 

VLT® AutomationDrive from any PROFIsafe host, 

up to Safety Integrity Level SIL  2 according 

to EN  IEC 61508 and EN IEC 62061, Perfor-

mance Level PL d, Category 3 according to 

EN  ISO  13849-1.

„

 PROFIsafe device  

(in combination with MCA 120)

„

 Replacement of external safety equipment

„

 2 safe programmable inputs

„

 Safe LCP copy

„

 Dynamic commissioning report

Ordering number 

130B9860 coated 

(Class 3C3/IEC 60721-3-3)

VLT® PTC Thermistor Card  

MCB 112

The VLT® PTC Thermistor Card 

MCB 112 enables improved surveillance of the 

 motor  condition compared to the built-in ETR 

 function and thermistor terminal.

„

 Protects the motor from overheating

„

 ATEX-approved for use with Ex d and  

Ex e motors

„

 Uses Safe Torque Off function, which is 

approved in accordance with SIL 2 IEC 61508

Ordering number

130B1137 coated 

(Class 3C3/IEC 60721-3-3)

VLT® Sensor Input Card  

MCB 114

This option protects the motor from being 

overheated by monitoring the temperature of 

bearings and windings in the motor. 

„

 Protects the motor from overheating

„

 3 self-detecting sensor inputs for 2 or 3 wire 

PT100/PT1000 sensors

„

 1 additional analog input 4-20 mA

Ordering number 

130B1172 standard

130B1272 coated 

(Class 3C3/IEC 60721-3-3)

VLT® Safety Option  

MCB 150 and MCB 151

The VLT ® Safety Options MCB 150 and  

MCB 151 expand the Safe Torque Off (STO) 

function, which is integrated in a standard  

VLT® AutomationDrive. Use the Safe Stop 1 

(SS1) function to perform a controlled stop 

before removing torque. Use the Safely- Limited 

Speed SLS function to monitor whether a 

specified speed is exceeded.

The functions can be used up to PL d accord-

ing to ISO 13849-1 and SIL 2 according to 

IEC 61508. 

„

 Additional standards-compliant safety 

functions

„

 Replacement of external safety equipment

„

 Reduced space requirements

„

 2 safe programmable inputs

„

 1 safe output (for T37)

„

 Easier machine certification

„

 Drive can be powered continuously

„

 Safe LCP Copy

„

 Dynamic commissioning report

„

 TTL (MCB 150) or HTL (MCB 151) encoder as 

speed feedback

Ordering number 

130B3280 MCB 150, 130B3290 MCB 151

48

Danfoss Drives · DKDD.PB.302.A8.02  | Content |

Summary of Contents for VLT AutomationDrive FC 300 Series

Page 1: ...Intelligence to empower your industrial applications Versatile reliable and consistently awesome Selection Guide VLT AutomationDrive FC 300 Series drives danfoss com...

Page 2: ...ations 14 Increase precision accuracy and speed 16 Tailored safety 17 Free to connect 18 Customized commissioning experience 19 Modular simplicity A B and C enclosures 20 VLT Wireless Communication Pa...

Page 3: ...es both hardware and software enhancements that maximize performance and a new Ethernet platform for improved communication VLT AutomationDrive takes full advantage of all that the new digital age has...

Page 4: ...ves industry When you choose the VLT AutomationDrive you can count on the intelligent drive functions application know how proven quality and reliability and the support you need to make a seamless tr...

Page 5: ...tionDrive one of the most compact and cost efficient drives in the market Consistently awesome Simple start up VLT AutomationDrive is robust and intelligent but at the same time quick and easy to inst...

Page 6: ...construction principle allowing for more drives to fit into less space Application flexibility When you have a variety of applications it s best to select an AC drive that you can count on to meet all...

Page 7: ...t tests and adjusts the drive to the unique traits of your motor improving overall control and operating efficiency Enhancements to the AMA for both asynchronous and PM motors means the process takes...

Page 8: ...negatively impact sensitive equipment Built in EMC RFI protection with screened motor cables to Residential Category C1 to 50 m and C2 to 150 m provides the ability to operate without additional and...

Page 9: ...ed interface of the web server in the Ethernet based communication options each drive can be remotely accessed and monitored for operation and diagnostics purposes saving time and costs Intuitive main...

Page 10: ...endent manufacturer of AC drive solutions you can count on Danfoss to support all commonly used motor types and foster ongoing development as new technologies emerge Flexible modular and adaptable Bui...

Page 11: ...C link chokes and EMC filters which help to reduce grid pollution and reduce cost and efforts for external EMC components and wiring The IP20 version is optimized for side by side mounting in cabinets...

Page 12: ...oving the drive even when mounted side by side More time saving features An intuitive user interface with an award winning Local Control Panel LCP and common control platform that streamlines start up...

Page 13: ...er and Wastewater Refrigeration Marine and Offshore Mining and Minerals Metals Chemical Cranes and Hoists Elevators and Escalators Material handling Oil and Gas Textile Pumps Fans Compressors Conveyor...

Page 14: ...without motor feed back with no need for additional hardware With sensorless control no motor feedback best performance is achieved with a PM motor The perfor mance of sensorless control of induc tio...

Page 15: ...tion offset is adjust able by parameter Homing With sensorless control and closed loop control with an incremental encoder homing is required to create a reference for the physical position of 0 1000...

Page 16: ...and removes the need for mechanical cam discs and boxes Increase capacity In other cases manufacturers might want to increase the capacity of their packaging application This can be achieved with the...

Page 17: ...SS1 and SLS SMS functionality The option can be used in low and high demand applications SS1 offers ramp and time based functionality SLS can be configured both with and without ramp down on activatio...

Page 18: ...orld Regardless of your application or your preferred communication protocol AC drives have an extremely wide variety of communication protocols to select from In this way you can ensure that the AC d...

Page 19: ...parameter settings With MCT 10 you can control and configure your system simultaneously and monitor your entire system more effectively for faster monitoring diagnosis troubleshooting alarms warnings...

Page 20: ...5 Control terminals Specially developed removable spring loaded cage clamps add to reliability and facilitate easy commissioning and service 6 Fieldbus option All major industrial fieldbuses are supp...

Page 21: ...n page 17 4 3 9 6 7 5 8 10 2 1 The VLT Wireless Communication Panel LCP 103 8 communicates with MyDrive Connect an app which can be downloaded to iOS and Android based smart devices MyDrive Connect of...

Page 22: ...motion control option for user specific control algorithms and programs allows the integration of PLC programs 11 Conformally coated and ruggedized circuit boards All high power drive circuit boards a...

Page 23: ...sed energy efficiency VLT drives pass more than 98 of the supplied electrical energy on to the motor Only 2 or less is left in the power electronics as heat to be removed Energy is saved and electroni...

Page 24: ...LT drives can operate at full load in engine rooms with 50 C temperature and 55 C at reduced power close to for example pumps and thrusters There is no need for installation in air conditioned control...

Page 25: ...ss is removed directly outside the installation room Minimal airflow over electronics Complete separation between back channel cooling air and the internal electronics ensures efficient cooling Panel...

Page 26: ...the harmonic distortion in the mains network in accordance with IEC61000 3 12 Furthermore they increase the lifetime of the DC link capacitors and therefore the overall efficiency of the drive These...

Page 27: ...t EN IEC61800 3 Converter manufacturers must conform to EN61800 3 Category C1 First environment home and office Category C2 First environment home and office Category C3 Second environment Compliance...

Page 28: ...es such as 0 Imax On the 68 P and 69 N terminals RS 485 interface the drive can be controlled and monitored via serial communication 3 Phase power input DC bus Switch Mode Power Supply Motor Analog Ou...

Page 29: ...S485 interface Up to 115 kBaud Max load 10 V 15 mA Max load 24 V 200 mA Relay outputs Programmable relay outputs 2 Max terminal load AC on 1 3 NC 1 2 NO 4 6 NC power card 240 V AC 2 A Max terminal loa...

Page 30: ...156 1143 C4 C2 C2 C2 P37K 143 215 37 50 195 1400 C4 C2 C2 C2 A1 enclosure is only available as FC 301 T2 3 x 200 240 V AC normal overload Normal overload 110 1 min 10 min Enclosure size Type code Outp...

Page 31: ...55 75 144 1022 C4 C2 C2 C2 P75K 147 221 130 195 75 100 200 1232 C4 C2 C2 C2 A1 enclosure is only available as FC 301 T5 3 x 380 500 V AC normal overload Normal overload 110 1 min 10 min Enclosure size...

Page 32: ...C1 P45K 62 93 45 60 85 900 C3 C1 C1 C1 P55K 83 125 55 75 113 1100 C4 C2 C2 C2 P75K 100 150 75 100 137 1500 C4 C2 C2 C2 T6 3 x 525 600 V AC normal overload Normal overload 110 1 min 10 min Enclosure si...

Page 33: ...75K 87 130 5 83 124 5 75 75 129 1500 C2 C2 Note T7 drives are not UL certified Select T6 for UL certification T7 3 x 525 690 V AC normal overload Normal overload 110 1 min 10 min Enclosure size Type c...

Page 34: ...242 225 230 308 370 308 370 Depth 207 205 207 205 207 175 200 260 260 249 242 310 335 333 333 Depth with A B option 222 220 222 220 222 175 200 260 260 262 242 310 335 333 333 Depth with mains discon...

Page 35: ...2 enclosures only 8 Mains disconnect and load sharing B1 B2 C1 and C2 enclosures only D Load sharing terminals B1 B2 C1 C2 enclosures only 10 Hardware option A character 22 X Standard cable entries O...

Page 36: ...90 1160 1740 710 1000 1227 14244 F2 F4 F2 F4 P800 1460 2190 1380 2070 800 1200 1422 15466 F2 F4 F2 F4 T5 3 x 380 500 V AC normal overload Normal overload 110 1 min 10 min Enclosure size Type code Outp...

Page 37: ...P1M0 1108 1662 1060 1590 1000 1150 1079 12997 F2 F4 F2 F4 P1M2 1317 1976 1260 1890 1200 1350 1282 15763 F2 F4 F2 F4 T7 3 x 525 690 V AC normal overload Normal overload 110 1 min 10 min Enclosure size...

Page 38: ...6 218 3 282 2 407 9 511 5 1 dimensions with regeneration or load share terminals 2 D5h is used with disconnect and or brake chopper options 3 D6h is used with contactor and or circuit breaker options...

Page 39: ...710 1000 1227 14967 F12 F13 F12 F13 P800 1460 2190 1380 2070 800 1200 1422 16392 F12 F13 F12 F13 T5 6 x 380 500 V AC normal overload Normal overload 110 1 min 10 min Enclosure size Type code Output c...

Page 40: ...put power Conti nuous input current Esti mated power loss Protection rating IEC UL 3 x 525 550 V 3 x 551 690 V IP21 Type 1 IP54 Type 12 FC 302 Con IN Inter IMAX 60 s Con IN Inter IMAX 60 s kW 690 V Hp...

Page 41: ...VLT 12 pulse VLT 12 pulse 41 Content Danfoss Drives DKDD PB 302 A8 02...

Page 42: ...54 Type 12 cabinet light 230 V power outlet R5A IP54 Type 12 space heater cabinet light 115 V power outlet R5X IP54 Type 12 space heater cabinet light 230 V power outlet E5E IP54 Type 12 cooling out t...

Page 43: ...G 5 A 24 V supply customer use and external temperature monitoring H 5 A 24 V supply customer use J External temperature monitoring K Common motor terminals L 5 A 24 V supply common motor terminals M...

Page 44: ...3 361 542 200 300 381 9753 D2n D2n N250 480 720 443 665 250 350 472 11587 E9 E9 P315 600 900 540 810 315 450 590 14140 E9 E9 P355 658 987 590 885 355 500 647 15286 E9 E9 P400 695 1043 678 1017 400 550...

Page 45: ...priority Programmable to harmonics or displacement power factor Paralleling option Up to 4 units of same power rating in master follower Current Transformer Support Customer supply and field mounting...

Page 46: ...for industrial use and handles even the most demanding requirements EtherNet IP extends commercial off the shelf Ethernet to the Common Industrial Protocol CIP the same upper layer protocol and objec...

Page 47: ...ion towards the drive with an interval down to 4 ms in both directions This allows the option to participate in networks ranging from low performance up to servo applications EoE Ethernet over EtherCA...

Page 48: ...mproves flexibility by connecting safety devices within a plant The safety functions of the MCB 152 are implemented according to EN IEC 61800 5 2 The MCB152 supports PROFIsafe functionality to activat...

Page 49: ...or positioning applications in many industries Features Relative positioning Absolute positioning Touch probe positioning End limit handling software and hardware Control via I Os or fieldbus Mechanic...

Page 50: ...mm cable IP21 Type 1 NEMA 1 kit Ordering number 130B1121 For enclosure size size A1 130B1122 For enclosure size size A2 130B1123 For enclosure size size A3 130B1187 For enclosure size size B3 130B118...

Page 51: ...alance in load sharing ap plications where the DC side of the rectifier of multiple drives is connected together UL recognized for applications using load sharing When planning load sharing applicatio...

Page 52: ...Chopper IGBTs 6 Safe Torque Off with Pilz Safety Relay 6 Regeneration terminals 6 Common Motor Terminals 6 n n n n n n n n n n Emergency Stop with Pilz Safety Relay 6 Safe Torque Off Pilz Safety Relay...

Page 53: ...uired for larger motors Power for the starters is provided from the load side of any supplied contactor circuit breaker or disconnect switch If a Class 1 RFI filter option is ordered the input side of...

Page 54: ...ak short circuit and incorrect polarity detection Interface set up software If 3 PTC are required an MCB 112 control card option must be added Additional external temperature monitors This option is a...

Page 55: ...f the pedestal has openings for input air to cool the power components Ordering number D1h 400 mm kit 176F3631 D2h 400 mm kit 176F3632 D5h D6h 200 mm kit 176F3452 D7h D8h 200 mm kit 176F3539 Input pla...

Page 56: ...ry here https goo gl RT4366 DKDD PB 302 A8 02 Copyright Danfoss Drives 2018 01 Stronger on the outside more intelligent on the inside EtherNet IP and DeviceNet are trademarks of ODVA Inc Providing con...

Reviews: