Enclosure Power [hp] Recommended fuse
size
Recommended max-
imum fuse
Recommended circuit breaker
Eaton/Moeller
Maximum trip
level [A]
40
gG-80
C1
40
gG-80
gG-160
NZMB2-A200
160
50
gG-100
60
gG-160
C2
75
aR-200
aR-250
NZMB2-A250
250
100
aR-250
C3
50
gG-100
gG-150
NZMB2-A200
150
60
gG-160
gG-160
C4
75
aR-200
aR-250
NZMB2-A250
250
100
aR-250
D1h/D3h
125
aR-315
aR-315
–
–
150
aR-350
aR-350
–
–
200
aR-400
aR-400
–
–
Table 15: 525–600 V, Enclosure Sizes A, B, C, and D
Enclosure Power [hp] Recommended fuse
size
Recommended max-
imum fuse
Recommended circuit breaker
Eaton/Moeller
Maximum trip lev-
el [A]
A2
1.0-5.0
gG-10
gG-25
PKZM0-25
25
A3
7.5
gG-10
gG-32
PKZM0-25
25
10
gG-16
A5
7.5
gG-10
gG-32
PKZM0-25
25
10
gG-16
B1
15
gG-25
gG-80
PKZM4-63
63
20
gG-32
25
gG-40
B2
30
gG-50
gG-100
NZMB1-A100
100
40
gG-63
B3
15
gG-25
gG-63
PKZM4-50
50
20
gG-32
B4
25
gG-40
gG-125
NZMB1-A100
100
30
gG-50
40
gG-63
C1
50
gG-63
gG-160
NZMB2-A200
160
AN354546796134en-000201 / 130R0954 | 25
Danfoss A/S © 2021.05
Electrical Installation
VLT®AutomationDrive EZ FC 321
Installation Guide