4 Installation
4.1.1 Mechanical Installation
The encapsulation of the filters have an IP 20 rating. The filters can be
mounted side by side with 60 mm (2,36 inches) clearance.
To other components and to the cabinet walls keep a horizontal clearance
of at least 70 mm (2,76 inches) and a vertical clearance of at least 150
mm (5,91 inches).
Only vertical installation is allowed (mains terminal at bottom).
For versions with bus bars (frame size E – H) it is nec-
essary to mount the added covers to the connectors in
order to achieve the protection type IP 20.
Illustration 4.1: Clearance surrounding the AHF filter
Below picture series shows mounting principles. All filters in frame E to H have to be mounted with an added terminal kit to comply with IP20 enclosure
rating. Please make sure that the terminal plastic cover back plate (see photo below) is mounted and fixed correctly before adding the terminal cover.
AHF 005/010 Operating Instructions
4 Installation