4.1.5 Fuses
In order to protect the installation against electrical and fire hazards, all filters in an installation must be short-circuited and over-current protected
according to national/international regulations. The filter must be protected against short-circuit and overload to avoid electrical or fire hazard and to
protect cables and filter from overheating. Danfoss recommends using fuses mentioned below to protect service personnel and equipment in case of an
internal failure in the filter.
Both filter and drive have to be connected against overload. If several frequency converters are to be connected to the one common harmonic filter, it
might be necessary to install fuses in front of both filter and drives.
In case of paralleled filter installation it might be necessary to install filters in front of each drive as well as in front of the entire installation to protect
both individual filters and drives.
I
AHF,N
Ordering Number
Ordering Number
Max Fuse Rating
[Amp]
AHF 005
AHF 010
[Amp]
10
175G6600
175G6622
16
19
175G6601
175G6623
35
26
175G6602
175G6624
50
35
175G6603
175G6625
50
43
175G6604
175G6626
63
72
175G6605
175G6627
125
101
175G6606
175G6628
160
144
175G6607
175G6629
250
180
175G6608
175G6630
315
217
175G6609
175G6631
315
289
175G6610
175G6632
500
324
175G6611
175G6633
500
370
175G6688
175G6691
630
Table 4.6: AHF005 and AHF010, 380-415V, 50Hz
I
AHF,N
Ordering Number
Ordering Number
Max Fuse Rating
[Amp]
AHF 005
AHF 010
[Amp]
19
130B2460
130B2472
35
26
130B2461
130B2473
50
35
130B2462
130B2474
50
43
130B2463
130B2475
63
72
130B2464
130B2476
125
101
130B2465
130B2477
160
144
130B2466
130B2478
250
180
130B2467
130B2479
315
217
130B2468
130B2480
315
289
130B2469
130B2481
500
324
130B2470
130B2482
500
370
130B2471
130B2483
630
Table 4.7: AHF005 and AHF010, 380-415V, 60Hz
IAHF,N
Ordering Number
Ordering nNumber
Max Fuse Rating
[Amp]
AHF 005
AHF 010
[Amp]
19
175G6612
175G6634
35
26
175G6613
175G6635
50
35
175G6614
175G6636
50
43
175G6615
175G6637
63
72
175G6616
175G6638
125
101
175G6617
175G6639
160
144
175G6618
175G6640
250
180
175G6619
175G6641
315
217
175G6620
175G6642
315
289
175G6621
175G6643
500
324
175G6689
175G6692
500
370
175G6690
175G6693
630
Table 4.8: AHF005 and AHF010, 440-480V, 60Hz
AHF 005/010 Operating Instructions
4 Installation
MG.80.C2.02 - VLT
®
is a registered Danfoss trademark
21