I
AHF,N
Ordering Number
Ordering Number
Max Fuse Rating
[Amp]
AHF 005
AHF 010
[Amp]
10
175G6644
175G6656
16
19
175G6645
175G6657
35
26
175G6646
175G6658
50
35
175G6647
175G6659
50
43
175G6648
175G6660
63
72
175G6649
175G6661
125
101
175G6650
175G6662
160
144
175G6651
175G6663
250
180
175G6652
175G6664
315
217
175G6653
175G6665
315
289
175G6654
175G6666
500
324
175G6655
175G6667
500
Table 4.9: AHF005 and AHF010, 500-525V, 50Hz
I
AHF,N
Ordering Number
Ordering Number
Max Fuse Rating
[Amp]
AHF 005
AHF 010
[Amp]
43
130B2328
130B2293
63
72
130B2330
130B2295
125
101
130B2331
130B2296
160
144
130B2333
130B2298
250
180
130B2334
130B2299
315
217
130B2335
130B2300
315
289
130B2301
500
324
130B2302
500
370
130B2304
630
Table 4.10: AHF005 and AHF010, 690V, 50Hz
NB!
See the section on fuses in the
Design Guide
.
4.1.6 Over Temperature Switch
The Danfoss harmonic filters AHF 005 and AHF 010 are equipped with a galvanic isolated thermal switch (not PELV), that is closed under normal
operating conditions and open if the filter is overheated.
Example: Connect terminal A of the harmonic filter to terminal 12 or13
(voltage supply digital input, 24V) of the Danfoss frequency converter and
terminal B to terminal 27 (digital input “Coast Inverse”) the frequency
converter will let go of the motor (coasting) and thereby unload the filter
if an over temperature is detected.
When connecting the A/B terminals directly to terminal 12 and 27 of the drive, Protective Extra Low Voltage (PELV) can no longer
be guaranteed!
NB!
A controlled ramp down within 30 s is allowed without causing overheat damage to the filter.
4 Installation
AHF 005/010 Operating Instructions
22
MG.80.C2.02 - VLT
®