380 - 415V
380 - 415V
440 - 480V
500 - 525V
690V
50Hz
60Hz
60Hz
50Hz
50Hz
I
AHF,N
Contactor Rating
Contactor Rating
Contactor Rating
Contactor Rating
Contactor Rating
kVAr
kVAr
kVAr
kVAr
kVAr
10 A
2
2
19 A
4
5
5
4
26 A
6
7
7
6
35 A
7
9
10
8
43 A
9
11
12
11
16
72 A
15
18
20
18
27
101 A
22
26
27
25
34
144 A
29
35
39
35
50
180 A
37
44
51
46
61
217 A
44
53
69
53
79
289 A
58
70
78
74
101
324 A
66
79
87
85
121
370 A
73
88
99
135
Table 4.5: Capacitor disconnect ratings.
NB!
Only switch the contactor at less than 20% output power. Allow minimum 240 seconds for the capacitors to discharge before turning
on again.
Only use cables complying with local regulations.
AHF 005/010 Operating Instructions
4 Installation
MG.80.C2.02 - VLT
®
is a registered Danfoss trademark
19