background image

VLT® 5000 Crane

Appendix

than unscreened cables. If the leakage current is not

filtered, it will cause greater interference on the mains

in the radio frequency range below approx. 5 MHz.

Since the leakage current (I

1

) is carried back to the unit

through the screen (I

3

), there will in principle only be

a small electro-magnetic field (I

4

) from the screened

motor cable according to the below figure.

The screen reduces the radiated interference, but

increases the low-frequency interference on the mains.

The motor cable screen must be connected to the

frequency converter enclosure as well as on the motor

enclosure. The best way of doing this is by using

integrated screen clamps so as to avoid twisted screen

ends (pigtails). These increase the screen impedance

at higher frequencies, which reduces the screen effect

and increases the leakage current (I

4

).

In the cases when the screen is to be placed on

a mounting plate for the frequency converter, the

mounting plate must be made of metal, because

the screen currents are to be conveyed back to the

unit. It is also important to ensure good electrical

contact from the mounting plate through the mounting

screws to the frequency converter chassis.

NB!:

Please note, however, that when unscreened

cables are used, some emission requirements

are not complied with, although the immunity

requirements are complied with.

In order to reduce the interference level from the

system overall (unit + installation) as far as possible,

it is important to make motor and brake cables as

short as possible. Cables with a sensitive signal level

must not be alongside motor and brake cables. Radio

interference higher than 50 MHz (airborne) will be

generated especially by the control electronics.

MG.50.N4.02 - VLT is a registered Danfoss trademark

115

Summary of Contents for VLT 5042

Page 1: ...VLT 5000 Crane Rev 2004 03 29 www danfoss com drives 175R0259 MG50N402 MG50N402 MG50N402 VLT 5000 Crane Operating Instructions Operating Instructions...

Page 2: ...hanical Installation 24 Installation of VLT 5042 5062 400 500 V Compact IP20 IP00 24 Installation of VLT 5072 5202 400 500 V Compact IP20 IP00 25 Electrical Installation 26 RFI switch 33 LCP Local Con...

Page 3: ...VLT 5000 Crane Appendix 92 Trouble shooting 92 Derating for air pressure 94 Efficiency 113 General aspects of EMC emissions 114 MG 50 N4 02 VLT is a registered Danfoss trademark 2...

Page 4: ...e Operating instructions Software version 20 3x These operating instructions can be used for VLT 5000 Crane frequency converters with software version 20 3x See software version number in parameter 62...

Page 5: ...requency converter is connected to mains Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs 7 Please note that the frequency...

Page 6: ...c technical publications on the VLT 5000 Crane and are delivered with the product When reading these Operating Instructions you come across different symbols that require special attention The symbols...

Page 7: ...or UM The voltage transmitted to the motor fM The frequency transmitted to the motor Break away torque VLT The efficiency of the frequency converter is defined as the ratio between the power output an...

Page 8: ...nel is detachable and may as an alternative be installed up to 3 metres away from the frequency converter ie in a front panel by means of the installation kit option Flux Vector If compared with stand...

Page 9: ...e parameters On line parameters are activated immediately after the data value is changed Off line parameters are not activated until OK has been entered on the control unit CT characteristics Constan...

Page 10: ...ures reliable galvanic isolation on all control terminals and integrated electronic thermal protection on the motor Function and System Description With VLT 5000 Crane the speed is infinitely varied i...

Page 11: ...reases the working range as it is possible to switch between normal load and heavy load VLT 5000 will optimise the motor control to the selected gear stage on the basis of the signal on terminal 29 se...

Page 12: ...g of system brake This means that the whole working range from 0 3000 RPM can be used and the crane system brake is controlled at approx 0 RPM Fault Status at Remote and Local Control Brake fault 1 VL...

Page 13: ...derating being required The current is split into magnetising and torque generating parts and provides for much better and quicker estimation of the actual motor loads It is now possible to compensat...

Page 14: ...s is given on LEDs placed near the encoder terminals for each channel as well as for the supply voltage for the encoder Green LED turned on means channel or voltage OK Reliable galvanic isolation In t...

Page 15: ...VLT 5000 Crane Key Diagram for VLT 5000 Crane 5042 5102 400 500 V MG 50 N4 02 VLT is a registered Danfoss trademark 14...

Page 16: ...VLT 5000 Crane Introduction Key Diagram for VLT 5000 Crane 5122 5202 400 500 V MG 50 N4 02 VLT is a registered Danfoss trademark 15...

Page 17: ...1 minute Digital Inputs Number of digital inputs 9 Voltage level 0 24 V DC PNP positive logics Voltage level logical 0 5 V DC Voltage level logical 1 10 V DC Max voltage on input 28 V DC Input resist...

Page 18: ...at analogue output 0 4 20 mA Max load to ground terminal 39 at analogue output 500 Accuracy of analogue output Max error 1 5 of full scale Resolution on analogue output 8 bit NOTE All digital and ana...

Page 19: ...ction for control cables 0 75mm2 AWG Max cross section for serial communication 0 75mm2 AWG NOTE Max cable cross section for motor and brake see Installation Accuracy of Display Readout Parameters 009...

Page 20: ...x For more information on derating see Special Conditions in Appendix VLT 5000 Crane Protection Electronic motor thermal protection against overload Electronic thermal protection against overload Temp...

Page 21: ...PVLT N HP 30 41 50 Max cable cross section to motor and brake mm 2 AWG 2 3 IP20 50 0 50 0 Rated input current IL N S3 60 A 400 V 51 62 76 Max cable cross section power mm 2 AWG 2 3 35 2 50 0 50 0 Max...

Page 22: ...120 2x35 2x70 Max cable cross section to motor 400 500 V AWG 2 3 3 0 4 0 2x2 0 2x350 MCM Max cable cross section to brake 400 500 V AWG 2 4 3 0 4 0 2x3 2x2 0 Max input current IL MAX S3 60 A 400 V 89...

Page 23: ...LITTEL FUSE may substitute KLNR fuses for 240 V drives L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives A50X f...

Page 24: ...enclosure 400 500 V VLT type A mm B mm C mm a mm b mm ab be mm l r mm 5042 5062 800 308 296 780 270 200 0 5072 5102 800 370 335 780 330 225 0 ab Min space above enclosure be Min space below enclosure...

Page 25: ...the max temperature stated for the frequency converter and that the 24 hour average temperature is not exceeded The max temperature and 24 hour average can be seen from the General Technical Data Enc...

Page 26: ...llows 1 Add up the values of P for all VLT 5000 Crane to be installed at the same panel P W 2 Determine the air inlet temperature tIN and the air outlet temperature tOUT C or K 3 Calculate the necessa...

Page 27: ...er s or certified electrician s responsibility to ensure correct earthing and protection in accordance with applicable national and local norms and standards All terminals for the control cables are l...

Page 28: ...er 0 75 Pulse signal B from encoder 90 76 Inverted pulse signal B from encoder 90 77 Zero pulse signal from encoder 78 Inverted zero pulse signal from encoder 49 5 V supply to encoder 47 Common for en...

Page 29: ...twisted screen ends pigtails is to be avoided since these spoil the screening effect at higher frequencies If it is necessary to break the screen to install a motor isolator or motor contactor the sc...

Page 30: ...rmoured Connect the screen to the metal cabinet of the frequency converter and to the metal cabinet of the brake resistor by means of cable clamps Dimension the cross section of the brake cable to mat...

Page 31: ...8 mm Allen wrench 5122 53024 19 M10 bolt 1 Brake terminals 3 0 Nm Nut M6 2 Brake and loadsharing 14 Nm M6 Allen screw 3 IP54 with RFI Line terminals 6Nm Screw M6 5 mm Allen wrench 4 Loadshare and bra...

Page 32: ...5 interface serial communication Switch 4 is used for separating the common potential for the internal 24 V DC supply from the common potential of the external 24 V DC supply NB Please note that when...

Page 33: ...act IP 20 VLT 5072 5102 400 500 V Compact IP 00 without disconnect and fuse VLT 5122 5302 400 500 V Compact IP 00 without disconnect and fuse VLT 5202 5302 400 500 V MG 50 N4 02 VLT is a registered Da...

Page 34: ...unit Check that the mains supply has been disconnected before operating the RFI switch NB Open RFI switch is only allowed at factory set switching frequencies NB The RFI switch disconnects the capacit...

Page 35: ...screen with a lower ZT is more effective than a screen with a higher ZT ZT is rarely stated by cable manufacturers but it is often possible to estimate Z T by looking at and assessing the physical des...

Page 36: ...y converter If the earth potential between the frequency converter and the PLC etc is different electric noise may occur that will disturb the whole system This problem can be solved by fitting an equ...

Page 37: ...is displayed via a 4 line alphanumeric display which during normal operation will be able to continuously display 4 items of operating data and 3 operating modes During programming all information nee...

Page 38: ...If certain threshold values are exceeded the alarm and or warning LED lights up concurrently with a status and alarm text on the control panel Display Read Out State The display read out state can be...

Page 39: ...the example Frequency has been selected as variable via parameter 009 During normal operation another variable can immediately be read out by using the keys Read out state II Switching between read o...

Page 40: ...is shown in line 4 Changing data Regardless of whether a parameter has been selected under the Quick menu or the Menu mode the procedure for changing data will be the same Pressing the CHANGE DATA key...

Page 41: ...iable Change of NumericData Value If the chosen parameter represents a numeric data value a digit is first selected by means of the keys 50 0 HZSETUP 1 FREQUENCY 102 MOTOR POWER 0 37 KW Then the chose...

Page 42: ...US VAR 1 1 VAR 1 2 VAR 1 3 1500 RPM FREQUENCY 0 KEYB DISPLAY 1500 RPM 001 LANGUAGE ENGLISH FREQUENCY 001 LANGUAGE ENGLISH 1500 RPM FREQUENCY 001 LANGUAGE ENGLISH 1500 RPM 001 LANGUAGE ENGLISH DATA CHA...

Page 43: ...are the following Level 0 Danfoss service not accessable Level 1 Commissioning 110775 Level 2 Normal operation 000002 NB NOTE that level 1 and level 2 passwords must be re entered after each power up...

Page 44: ...B Note that the fwd rev function is not active in crane profile The function only functions if the VLT is programmed to run as a normal VLT 5000 see parameter 512 START is used to start the frequency...

Page 45: ...500 kW Depends on unit No 9 1 6 1 103 Motor voltage 200 500 V Depends on unit No 21 0 6 1 104 Motor frequency 24 1000Hz Depends on unit No 28 0 6 1 105 Motor current 0 01 1VLT MAX Depends on unit No 2...

Page 46: ...imit motor mode 0 0 170 160 Yes 24 1 6 1 222 Torque limit generator operation 0 0 170 160 Yes 24 1 6 1 234 Missing motor phase Enable Yes 0 0 5 1 235 Phase loss monitor Enable No 0 0 5 1 236 Low speed...

Page 47: ...min scaling 0 0 20 0mA 4 0 mA Yes 22 4 5 1 316 Terminal 60 max scaling 0 0 20 0mA 20 0 mA Yes 22 4 5 1 317 Time out 0 sec 0 sec Yes 4 0 5 1 318 Function after time out Off Yes 0 0 5 1 319 Terminal 42...

Page 48: ...o 8 2 7 2 603 Operation Data Power ups No 0 0 6 2 604 Operation Data Over temps No 0 0 6 2 605 Operation Data Over volts No 0 0 6 2 615 Fault log Error code No 0 0 5 2 616 Fault log Time No 0 1 7 2 61...

Page 49: ...26 Gear inertia 2 0 1 Depends on unit No 0 4 6 1 727 Mean radius 2 0 2 Depends on unit No 0 3 6 1 740 Power limit function Constant power No 0 0 5 1 741 Mechanical speed N1 Depends on unit No 11 0 6 1...

Page 50: ...VLT 5000 Crane Programming Parameter survey factory setting display text value for use in communication via serial communication port MG 50 N4 02 VLT is a registered Danfoss trademark 49...

Page 51: ...keys 5 An external control command that can be connected to the digital inputs NB The FWD REV key is located on the LCP control unit 003 LOCAL REFERENCE Function This parameter allows manual setting o...

Page 52: ...basis of configuration in parameter 100 Hz Hz and rpm Frequency Hz gives the motor frequency ie the output frequency from the frequency converter Motor speed RPM corresponds to the present motor speed...

Page 53: ...meter 009 for choices Motor current A Function This parameter enables a choice of the second of the three data values to be shown on the display line 1 position 2 For Display read outs press the DIS P...

Page 54: ...able 0 is selected in this parameter the RESET key will be inactive However this is not possible when operating in crane profile NB When running in FC profile do not select Disable 0 unless an externa...

Page 55: ...at depends on the type of unit Description of choice Select a value that equals the nameplate data on the motor There are 4 possible undersizes or 1 oversize in comparison with the factory setting Als...

Page 56: ...eter 124 is to be activated Select Motor check 2 if the frequency converter is to check whether or not a motor has been connected 124 DC HOLD CURRENT Value 50 Function This parameter is used to mainta...

Page 57: ...factory setting the parameters are set accordingly to the motor name plates If these parameters are not set correctly it may cause a malfunction of the drive 150 STATOR RESISTANCE Value Ohm Depends on...

Page 58: ...arameter 157 FIELD WEAKENING SPEED Value 0 6000 RPM Depends on unit Function In this parameter the field weakening point for the Flux Vector control is set 158 IRONLOSS RESISTANCE Value 1 10000 10000...

Page 59: ...parameter 104 to 0 Hz or from the rated motor speed n M N provided there is no over voltage in the inverter because of regenerative operation of the motor or if the generated current reaches the torqu...

Page 60: ...hoice In order to protect the motor from reaching pull out torque the factory setting is 1 6 x the rated motor torque calculated value If a setting in parameters 101 106 is changed parameters 221 222...

Page 61: ...sable is selected no alarm is given if a motor phase is missing The converter may be damaged when running with a missing input phase It is therefore recommended to keep the phase loss monitor function...

Page 62: ...itioning mode is only available when running in remote control If the signal is removed the frequency converter is to operate in normal mode Start lowering is selected when the frequency converter is...

Page 63: ...nverse is activated by interrupting the voltage to the terminal This means that if the terminal has no voltage the motor cannot run The stop will be effected in accordance with the selected ramp param...

Page 64: ...er 317 Time out and 318 Function after time out the value set must be higher than 1 Volt 310 AI 53 SCALE HIGH Value 0 10 0 Volt 10 0 Volt Function This parameter is used for setting the signal value t...

Page 65: ...ruled to jog frequency 3 overruled to max output frequency 4 overruled to stop with subsequent trip 5 319 AO 42 FUNCTION Value No operation NO OPERATION 40 0 100 Hz 0 20mA 0 100 HZ 0 20MA 41 0 100 Hz...

Page 66: ...20 mA An output signal is obtained which is proportional to 160 of the rated motor torque 160 yields 0 4 mA 0 yields 10 12 mA and 160 yileds 20 mA 321 AO 45 FUNCT Value Function On these analogue out...

Page 67: ...warning THERMAL WARNING 16 Unit ready and no thermal warning READY NO THERM WARN 17 Unit ready and no over undervoltage RDY NO OVER UNDERVOL 18 Control word bit 11 CTRL WORD BIT 11 19 Control word bit...

Page 68: ...the inputs The mains voltage is within the permitted voltage range Control word bit 11 The output is controlled by bit 11 in serial control word See Serial communication in Appendix Control word bit 1...

Page 69: ...er transmitted over 120 sec exceeds 100 of the monitoring limit parameter 402 and Warning 1 has been selected a warning will come up on the display The warning will disappear if the power goes below 8...

Page 70: ...giving an alarm trip locked if the brake resistor has short circuited or been disconnected or if the brake IGBT has short circuited 405 RESET MODE Value Manual reset MANUAL RESET 0 Reset at power up R...

Page 71: ...e frequency converter Parameter 604 Number of overtemperatures Gives the number of overtemperature faults that have been registered on the frequency converter s heat sink Parameter 605 Number of overv...

Page 72: ...s except parameters 603 605 can be initialised This function will not become active until the mains supply to the frequency converter has been turned off and then turned on again Description of choice...

Page 73: ...G 630 Communication option type COM OPTION 631 Communication ordering COM ORDERING Function The unit s main data can be read out from parameters 621 to 635 Type plate using the LCP control unit or ser...

Page 74: ...RD LEVEL 2 000002 Password level 1 PASSWORD LEVEL 1 110775 Function After entering the correct password the new protection level is shown in the LCP After power up the password is to be re entered in...

Page 75: ...ion Load Monitoring of load contacts 1 and 2 can be either disabled or enabled in this parameter 704 LOW SPD AT ERROR Value 200 200 RPM 50 RPM Function With this parameter you can choose the lowering...

Page 76: ...718 ENCODER MONITOR Value 0 DISABLE 0 1 ENABLE 1 Function This parameter makes it possible to choose between disable and enable in order not to monitor or to monitor the encoder hardware 720 DRUM INER...

Page 77: ...OWER LIMIT FUNC Value 0 CONSTANT POWER 0 1 USER DEFINED 1 2 OFF 2 Function With this parameter it is possible to choose between a speed limitation based on constant power or a speed limitation based o...

Page 78: ...e speed point for power speed curve at N4 Description of choice The parameter is limited between N3 par 745 speed and output speed high limit par 202 748 POWER AT N4 Value kW Depends on unit Function...

Page 79: ...alue kW Depends on unit Function Set the power loss at N2 Description of choice This parameter is limited to be less than or equal to the power at N1 757 Power Loss N3 Value kW Depends on unit Functio...

Page 80: ...Function Set the power loss at N7 Description of choice This parameter is limited to be less than or equal to the power at N6 factory setting display text value for use in communication via serial co...

Page 81: ...on the control card for ON see Switches 1 4 Bus Connection RS 232 The purpose of the RS 232 is to enable communication between a PC and one VLT With this communication it is possible to monitor progr...

Page 82: ...26 Data read out Motor thermal No 24 0 5 2 527 Data read out VLT thermal No 24 0 5 2 528 Data read out Digital input No 0 0 5 2 529 Data read out Term 53 analogue input No 21 2 3 2 530 Data read out T...

Page 83: ...ic and LOGIC AND 2 Logic or LOGIC OR 3 Function Parameters 503 508 allow a choice between controlling the frequency converter via the digital inputs and or via the serial port Description of choice Th...

Page 84: ...rt 1 Logic and 2 or Logic or 3 NB Note that this parameter is only available when the VLT 5000 Crane runs in FC profile Digital input 0 Dig input Ser port Function 0 0 Clockwise 0 1 Clockwise 1 0 Anti...

Page 85: ...mmunication port and the LCP display See also parameters 009 012 Display readout Description of choice Resulting reference parameter 515 Gives the resulting reference as a percentage in the range from...

Page 86: ...larm word parameter 538 Gives in Hex which alarm is on the frequency converter See Warning word extended status word and alarm word Control word parameter 539 Gives the present control word on the fre...

Page 87: ...02 the reference is set in parameter 003 The drive profile for the frequency converter is FC profile parameter 512 Right part Ramping The output frequency is now changed according to the present ramp...

Page 88: ...X 10 MOTOR TIME X X X 11 MOTOR THERMISTOR X X X 12 TORQUE LIMIT X X 13 OVER CURRENT X X 14 EARTH FAULT X X 15 SWITCH MODE FAULT X X 16 CURR SHORT CIRCUIT X X 17 STD_BUS TIMEOUT X X X 19 EE ERROR POWER...

Page 89: ...309 Check the wires to terminals 53 and 58 3 a No Motor The motor check function see parameter 122 indicates that no motor has been connected to the output of the frequency converter Check the motor...

Page 90: ...g or an alarm when the counter reaches 100 The fault is that the motor is overloaded by more than 100 for too long Check the load and that motor parameters 102 106 have been set correctly 11 Motor The...

Page 91: ...circuits the brake function is disconnected and the warning appears The frequency converter is still able to work although without the brake function Turn off the frequency converter and replace the b...

Page 92: ...sage The figure in square brackets is the fault code that can be seen in the fault log parameter 615 0 The brake resistor check carried out during power up indicates that the brake has been disconnect...

Page 93: ...tance If no check if the control card is overloaded If so disconnect all control signal plugs on the control card and check if the fault disappears If yes make sure that the 24 V supply is not short c...

Page 94: ...tion are OK If yes call Danfoss for assistance If the READY LED is NOT active check if the connections to the brake control card are OK then follow the steps from checking the braking and overload LED...

Page 95: ...onnected to a frequency converter it is necessary to check whether the cooling of the motor is adequate At low RPM values the motor fan is not able to supply the required volume of air for cooling Thi...

Page 96: ...haracter begins with a start bit Subsequently 8 data bits are transferred Each character is secured via a parity bit which is set to 1 when there is even parity i e an even number of binary 1 s in the...

Page 97: ...active Bit 0 6 Frequency converter address 1 126 Bit 0 6 0 Broadcast The slave sends the address byte back to the master in the reply telegram in unchanged form Example A telegram is sent to frequency...

Page 98: ...ord 0 0 1 1 Parameter description element transferred 0 1 1 1 Command cannot be performed 1 1 1 1 Text transferred If the command cannot be executed the slave will send this reply 0111 and give the fo...

Page 99: ...ransferred read the telegram length is variable since the texts have different lengths The telegram length is stated in the 2nd byte of the telegram called LGE Parameters 621 631 nameplate data have d...

Page 100: ...d high 0 0 Load low 0 1 Trip 1 0 No function 1 1 Bit 02 No function Positioning Makes the motor turn with reduced speed according to parameters 106 Motor Nominal Speed and 205 Max reference Bit 02 0 m...

Page 101: ...the frequency converter is running and that positioning is active Bit 07 No warning Warning Bit 07 0 means that there are no warnings Bit 07 1 means that a warning has appeared Bit 08 Not on referenc...

Page 102: ...e as to how Bit 06 is to be combined gated with the corresponding function on the digital inputs Bit 07 No function reset Reset of trip Bit 07 0 means there is no reset Bit 1 means that a trip is rese...

Page 103: ...no warnings Bit 07 1 means that a warning has appeared Bit 08 Not on reference on reference Bit 08 0 means that the motor is running but speed torque do not equal the reference Bit 08 1 means that the...

Page 104: ...form of a 16 bit word 16384 4000 Hex corresponds to 100 refMIN refMAX 0 16384 0 4000 Hex 0 100 refMIN refMAX Actual output speed The value of the actual output of the freqruency converter is transmit...

Page 105: ...00 00 02 0C XX XX XX XX XX All numbers are in hex format Pcd 1 and pcd 2 from example 2 can be used and added to the example which means that it will be possible to control the drive and read the curr...

Page 106: ...ive parameter 14 Array 13 Parameter value can only be reset 12 Parameter value different from factory setting 11 Text available 10 Additional text available 9 Read only 8 Upper and lower limit not rel...

Page 107: ...he answer to the master will be in PWELOW Conversion and Unit of measurement index 4 The Conversion and unit of measurement command indicates the conversion of a parameter and the unit of measurement...

Page 108: ...e h 74 j 0 8 Energy kWh W 0 9 Power kW 3 1 s 0 11 Speed 1 min RPM 67 16 Torque Nm 0 K 0 17 Temperature C 100 21 Voltage V 0 22 Current A 0 24 Ratio 0 27 Relative change 0 28 Frequency Hz 0 Conversion...

Page 109: ...at PKE 4001 4 in the PKE field indicates a Read Parameter Description and 01 indicates parameter number 001 Language IND 0006 6 indicates that Names is required The response from the frequency convert...

Page 110: ...returns an answer in PWELOW If a bit is logic 1 the condition is true according to the table below Bit Description 0 Special Default Value 1 Special Upper Limit 2 Special Lower Limit 7 LCP Access LSB...

Page 111: ...ust be sent to the VLT frequency converter STX LGE ADR PKE IND PWEHIGH PWELOW PCD1 PCD2 BCC 02 0E 01 F0 01 00 01 00 00 00 00 XX XX XX XX XX STX 02 Start byte LGE 0E Length of the remaining telegram AD...

Page 112: ...isolation Earth leakage current Earth leakage current is primarily caused by the capacitance between motor phases and the motor cable screen When an RFI filter is used this contributes additional leak...

Page 113: ...he inverter turns off to protect the transistors and the intermediate circuit capacitors when a certain voltage level is reached Mains drop out During a mains drop out VLT 5000 Crane continues until t...

Page 114: ...t In general the efficiency is just as good as with mains operation The efficiency of the motor depends on the type of motor In the range of 75 100 of the rated torque the efficiency of the motor is p...

Page 115: ...standard This normally reduces the input current IRMS by 40 The voltage distortion on the mains supply depends on the size of the harmonic currents multiplied by the mains impedance for the frequency...

Page 116: ...reduces the screen effect and increases the leakage current I 4 In the cases when the screen is to be placed on a mounting plate for the frequency converter the mounting plate must be made of metal be...

Page 117: ...own how often to brake and by how much power braking is effected The resistor ED which is often used by motor suppliers when stating the permissible load is an indication of the duty cycle at which th...

Page 118: ...occurs power dissipation in the brake resistor can only be prevented by using a mains switch or contactor to disconnect the mains for the frequency converter The contactor can be controlled by the fre...

Page 119: ...P 20 SB R3 175Z4831 5102 65 IP 20 SB R3 175Z4408 5152 90 IP 00 SB R1 176F2034 5202 110 IP 00 SB R1 176F2035 LCP Control unit with display and keypad SB Standard unit with without control unit and inte...

Page 120: ...Parameters 85 Derating for Ambient Temperature 94 Derating for Running at Low Speed 94 Derating hoisting 75 Derating lowering 75 Description of Functions 10 Digital Inputs 16 Digital Pulse and Analog...

Page 121: ...1 75 Mean radius 2 76 Mechanical brake off delay 75 Mechanical brake on delay 75 Mechanical speed N1 76 Mechanical speed N2 76 Mechanical speed N3 77 Mechanical speed N4 77 Mechanical speed N5 77 Mech...

Page 122: ...esistor 116 Serial Communication 95 Signal output 26 67 Signal output 46 66 Speed PI lowpass filter time 69 Start 82 Start torque 74 Stator Leakage Reactance 56 Stator Resistance 56 Status Word in Cra...

Page 123: ...VLT 5000 Crane Rev 2004 03 29 www danfoss com drives 175R0259 MG50N402 MG50N402 MG50N402 VLT 5000 Crane Operating Instructions Operating Instructions...

Reviews: