VLT® 5000 Crane
Technical
Data
■
Mains supply 3 x 400-500 V
According to international
requirements
VLT type
5072
5102
5152
5202
Output
current
I
VLT,N
[A] (S3 60%) (400-500 V)
100
139
201
246
I
VLT, MAX
(60 s) [A] (400-500 V)
159
221
301
369
Output
S
VLT,N
(S3 60%) [kVA]
(400-500 V)
67.5
93.9
135.8
166.2
Typical shaft output P
VLT,N
[kW]
45
65
90
110
Typical shaft output P
VLT,N
[HP]
61
89
125
150
Max. cable cross-section to motor
(400-500 V) [mm
2
]
3)
95
120
2x70
2x185
Max. cable cross-section to brake
(400-500 V) [mm
2
]
4)
95
120
2x35
2x70
Max. cable cross-section to motor
(400-500 V) AWG]
2) 3)
3/0
4/0
2x2/0
2x350
MCM
Max. cable cross-section to brake
(400-500 V) AWG]
2) 4)
3/0
4/0
2x3
2x2/0
Max input current
I
L,MAX
(S3 60%) [A] (400 V)
89
124
186
224
Max. cable cross-section to power
(400-500 V) [mm
2
]
3)
95
120
2x70
2x185
Max. cable cross-section to power
(400-500V) [AWG]
2) 3)
3/0
4/0
2x2/0
2x350
MCM
Efficiency
0.96-
0.97
0.96-
0.97
0.97-
0.98
0.97-
0.98
Weight IP 20 EB/IP 00
[kg]
109
109
89
134
Power loss at max. load [W]
1860
2250
2828
3231
Enclosure
IP20
IP20
IP00
IP00
1. For type of fuse see section
Fuses
.
2. American wire gauge.
3. Connection Dual M10 screws.
4. Connection Dual M8 screws.
MG.50.N4.02 - VLT is a registered Danfoss trademark