background image

VLT

®

 5000 and Interbus CMD

7

MN.50.U1.02 - VLT is a registered Danfoss trademark

To activate the new settings with PCD, the CMD

need to read the configuration from the VLT

frequency converter again.

The process data should start at address 20 and

this has to be assigned to the master and slave.

Click on controller board and select 

Process data

.

The Process data should now be 64 bits, corre-

sponding to 4 words: control word, reference, PCD

1 and PCD 2.

The Address Monitor shows the I/O area.

P20 Input 0F07 Hex:

Shows the status word from the VLT frequency

converter.

P20 Output 047C Hex:

Here you can write the control word to the VLT

frequency converter.

See 

Configuring of the CMD and VLT 5000

 for how

to parametize the system.

When the system is running, change the state to

Monitor.

Click on controller board and select Address

Monitor.

P22 Input 201E:

Shows the actual reference from the VLT frequency

converter.

P22 Output 2000 Hex:

Here you can write a reference to the VLT frequency

converter.

P24 Input 008D Hex (PCD 1):

This I/O area shows the actual motor current in Hex

(parameter 520 

Data readout: Motor current

).

The value corresponds in decimal to 141. But as

Parameter 520 has a conversion index of -2 (see

Manual) the actual motor current is 1.41 Amp.

P24 Output 03E8 Hex (PCD 1):

The same I/O area as reading of motor current was

set up to write to parameter 207 

Ramp up time 1

.

03E8 hex corresponds to 10 sek in ramp up time as

this parameter has a conversion index of -2.

P26 Input 00FB Hex (PCD 2):

This I/O area shows the actual motor frequency in

Hex (parameter 518 

Data readout: Frequency

).

The value corresponds in decimal to 251. But as

Parameter 518 has a conversion index of -1 (see

Manual) the actual motor frequency is 25.1 Hz.

P26 Output 0000 Hex (PCD 2):

This output is not configurated.

Summary of Contents for VLT 5000

Page 1: ...e Green PCP Communication running NO PCP Communication running UL Power OK Green Voltage within permissible range No Voltage All examples in this instruction are shown with a PLC card as an Interbus m...

Page 2: ...ad In is finished Please look at the bottom of the screen After the Read In CMD will indicate each VLT frequency converter with a DriveCom symbol a station number and an ID number Next step is to conf...

Page 3: ...ram profile must be set to Fieldbus option If you change the operating state from Online to Monitor you can write the control word and refe rence to the VLT frequency converter In Monitor state you ca...

Page 4: ...rol for controlling the VLT frequency converter Please notice that the control word will change when you change the states The control word is now 7F Hex Press Close The Manufactured Specific bits are...

Page 5: ...st row 55F1 Hex corresponds to 22001D This means that all VLT 5000 parameters simply can be accessed by adding 22000D to the VLT 5000 parameter For example if you want to write to parameter 207 Ramp u...

Page 6: ...PCD data The data for the VLT frequency converter in our PLC program starts at address 20 So we have to map address 20 to the Interbus card in the VLT frequency converter This is done with the CMD to...

Page 7: ...ontroller board and select Address Monitor P22 Input 201E Shows the actual reference from the VLT frequency converter P22 Output 2000 Hex Here you can write a reference tothe VLT frequency converter P...