4
MN.50.U1.02 - VLT is a registered Danfoss trademark
VLT
®
5000 and Interbus CMD
■
■
■
■
■
Drivecom profile, cont.
By clicking Settings you can setup the Drivecom
monitor.
In
Manufactured Specific Control bits
Danfoss have
choosen to implement Jog, Setup select and
Reversering, and in
Manufactured Specific Status
the Running Status bit is implemented.
Press OK when the Monitor settings are done.
Click on Device Control for controlling the VLT
frequency converter. Please notice that the control
word will change when you change the states.
The control word is now 7F Hex. Press Close.
The
Manufactured Specific bits
are now added to
the Drivecom monitor.
Type a reference in rpm below
Set Speed
and click
on Write to send the reference to the VLT frequency
converter. The rpm value can now be seen in the
VLT display as a reference from 0 - 100 %.
Click 4 for
Ready to Switch On
and click 2 for
Switch On.
By Clicking 5 the VLT frequency converter should
start the motor. Do not forget to set VLT parameter
502 Coasting to
Bus.