 5000 and Interbus CMD

 Process and PCD data

The process data is spilt up in two parts, a fixed 2

words data part for controlling the VLT frequency

converter and a flexible part, called PCD, that

can consist of 7 words.

For controlling the VLT 5000 you can select

between the FC profile or Drivecom profile (VLT

parameter 512).

Please have a look at the Interbus operating

instructions for further description of each profile.

PCD data is very useful if you need a constant

update of process parametersvariables, for

example motor current or torque.

MRV PCD1 PCD2

CTW

PCD4

PCD7

PCD3

PCD5 PCD6

MAV PCD1 PCD2

STW

PCD4

PCD7

PCD3

PCD5 PCD6

Fixed

Fixed

Fixed

Fixed

Fixed

Fixed

Fixed

Fixed

Fixed

Fixed

User definable

User definable

User definable

User definable

User definable

User definable

User definable

User definable

User definable

User definable

 Programming example

The following example will show how to set up

process and PCD data.

The chosen profile is Drivecom profile and as PCD

data we will readout parameter 520 

Motor current

and 518 

Motor frequency

. We will also write to

parameter 207 

Ramp up time 1 

as PCD data.

The data for the VLT frequency converter in our PLC

program starts at address 20. So we have to map

address 20 to the Interbus card in the VLT

frequency converter. This is done with the CMD

tool.

First we have to setup the VLT frequency converter

to run with two PCD‘s. This is done in the

respective parameter 807 

PCD size select

 and

parameter 915/916 

PCD config. write/read.

PCD 1 has to be set to read the motor current via

parameter 520. This is done by setting sub index 1

in parameter 916 

PCD configuration read

 to 520.

PCD 2 has to be set to read parameter 518 

Motor

frequency

. Set sub index 2 to 518.

PCD 1 has to be set to write the ramp up time 1 via

parameter 207. This is done by setting sub index 1

in parameter 915 

PCD Configuration write

 to 207.

In parameter 807 

PCD size select

 you have to

assign the number of PCD‘s which the VLT

frequency converter is using.

Choose 

2 WORDS

 [2] and power down the VLT

frequency converter. At next power up the PCD‘s

will be active.

 0.0 Hz

SETUP

1

FREQUENCY

916 PCD CONFIG. READ

5

20

[1]

 0.0 Hz

SETUP

1

FREQUENCY

915 PCD CONFIG. WRITE

2

07

[1]

 0.0 Hz

SETUP

1

FREQUENCY

807 PCD SIZE SELECT

2  WORDS

 0.0 Hz

SETUP

1

FREQUENCY

916 PCD CONFIG. READ

5

18

[2]

PLC

CTW

MRV

PCD1

CTW

MRV

PCD1

FC profile

0-100%

Par. 520

Par. 207

Interbus

QW 20

QW 22

QW 24

IW 20

IW 22

IW 24

STW

STW

MAV

MAV

PCD1

PCD1

FC profile

0-100%

Par. 518

IW 26

PCD2

PCD2

Summary of Contents for VLT 5000

Page 1: ...e Green PCP Communication running NO PCP Communication running UL Power OK Green Voltage within permissible range No Voltage All examples in this instruction are shown with a PLC card as an Interbus m...

Page 2: ...ad In is finished Please look at the bottom of the screen After the Read In CMD will indicate each VLT frequency converter with a DriveCom symbol a station number and an ID number Next step is to conf...

Page 3: ...ram profile must be set to Fieldbus option If you change the operating state from Online to Monitor you can write the control word and refe rence to the VLT frequency converter In Monitor state you ca...

Page 4: ...rol for controlling the VLT frequency converter Please notice that the control word will change when you change the states The control word is now 7F Hex Press Close The Manufactured Specific bits are...

Page 5: ...st row 55F1 Hex corresponds to 22001D This means that all VLT 5000 parameters simply can be accessed by adding 22000D to the VLT 5000 parameter For example if you want to write to parameter 207 Ramp u...

Page 6: ...PCD data The data for the VLT frequency converter in our PLC program starts at address 20 So we have to map address 20 to the Interbus card in the VLT frequency converter This is done with the CMD to...

Page 7: ...ontroller board and select Address Monitor P22 Input 201E Shows the actual reference from the VLT frequency converter P22 Output 2000 Hex Here you can write a reference tothe VLT frequency converter P...