2

MN.50.U1.02 - VLT is a registered Danfoss trademark

VLT

®

 5000 and Interbus CMD

 Configuring of the CMD and VLT 5000

The first step is to connect all Interbus slaves to the

master and power up all units.

Start the IBS CMD software and choose a new

project from 

File

 and 

New.

The screen should now look like this:

Next step is to read the slaves on the bus system.

Click on 

Configuration frame 

and click on the right

mouse button. Select 

Read In

 and choose 

Startup

without PDP

.

The state will be changed from Offline to Online

when the Read In is finished. Please look at the

bottom of the screen.

After the Read In, CMD will indicate each VLT

frequency converter with a DriveCom symbol, a

station number and an ID number.

Next step is to configuring the Interbus system. This

is done by clicking on the VLT symbol and pressing

the right mouse button. Select 

Description

.

Here you can type a Station name, Device name

and a Device number.

Click on 

Parameter Channel

.

By message lenght transmit and receive enter 246

Byte and select Get-OD (long format). The message

length now corresponds to the internal buffer in the

VLT frequency converter. Get-OD (long format)

means that the master will read the English

parameter description text from the VLT frequency

converter.

Press OK twice.

Summary of Contents for VLT 5000

Page 1: ...e Green PCP Communication running NO PCP Communication running UL Power OK Green Voltage within permissible range No Voltage All examples in this instruction are shown with a PLC card as an Interbus m...

Page 2: ...ad In is finished Please look at the bottom of the screen After the Read In CMD will indicate each VLT frequency converter with a DriveCom symbol a station number and an ID number Next step is to conf...

Page 3: ...ram profile must be set to Fieldbus option If you change the operating state from Online to Monitor you can write the control word and refe rence to the VLT frequency converter In Monitor state you ca...

Page 4: ...rol for controlling the VLT frequency converter Please notice that the control word will change when you change the states The control word is now 7F Hex Press Close The Manufactured Specific bits are...

Page 5: ...st row 55F1 Hex corresponds to 22001D This means that all VLT 5000 parameters simply can be accessed by adding 22000D to the VLT 5000 parameter For example if you want to write to parameter 207 Ramp u...

Page 6: ...PCD data The data for the VLT frequency converter in our PLC program starts at address 20 So we have to map address 20 to the Interbus card in the VLT frequency converter This is done with the CMD to...

Page 7: ...ontroller board and select Address Monitor P22 Input 201E Shows the actual reference from the VLT frequency converter P22 Output 2000 Hex Here you can write a reference tothe VLT frequency converter P...

Reviews: