VLT

®

 5000 and Interbus CMD

3

MN.50.U1.02 - VLT is a registered Danfoss trademark

The VLT frequency converter is now set up and the

program can be downloaded to the PLC master.

This is done by clicking with the right mouse button

on the 

Controller board

.

Select 

Parameterization

 and 

Execute.

After the parameterization is done, the master will

start to run. If you are using a Siemens S7 or S5

master, the LCD will look like this:

 Drivecom profile

VLT 5000 has implemented the Drivecom profile in

the Interbus software. In order to be able to run with

the Drivecom profile, VLT parameter 512 

Telegram

profile 

must be set to 

Fieldbus option.

If you change the operating state from 

Online 

to

Monitor

 you can write the control word and refe-

rence to the VLT frequency converter. In Monitor

state you can also read and write to parameters.

Now you can start the built in Drivecom monitor in

CMD by clicking on the 

Controller board

 and clicking

on the right mouse button. Select 

Drivecom

.

The Drivecom monitor will now show 

Danfoss, VLT

5000, Profile: 21, 

in the upper left corner.

The Drivecom monitor is spilt up in three parts:

Analog Display, Control Word and Status word.

In the Analog Display part you can set a reference

and in the Control word part you can start and stop

the VLT frequency converter. In the Status word

part you can see the actual status word from the

VLT frequency converter.

Summary of Contents for VLT 5000

Page 1: ...e Green PCP Communication running NO PCP Communication running UL Power OK Green Voltage within permissible range No Voltage All examples in this instruction are shown with a PLC card as an Interbus m...

Page 2: ...ad In is finished Please look at the bottom of the screen After the Read In CMD will indicate each VLT frequency converter with a DriveCom symbol a station number and an ID number Next step is to conf...

Page 3: ...ram profile must be set to Fieldbus option If you change the operating state from Online to Monitor you can write the control word and refe rence to the VLT frequency converter In Monitor state you ca...

Page 4: ...rol for controlling the VLT frequency converter Please notice that the control word will change when you change the states The control word is now 7F Hex Press Close The Manufactured Specific bits are...

Page 5: ...st row 55F1 Hex corresponds to 22001D This means that all VLT 5000 parameters simply can be accessed by adding 22000D to the VLT 5000 parameter For example if you want to write to parameter 207 Ramp u...

Page 6: ...PCD data The data for the VLT frequency converter in our PLC program starts at address 20 So we have to map address 20 to the Interbus card in the VLT frequency converter This is done with the CMD to...

Page 7: ...ontroller board and select Address Monitor P22 Input 201E Shows the actual reference from the VLT frequency converter P22 Output 2000 Hex Here you can write a reference tothe VLT frequency converter P...

Reviews: