MG.10.O1.02 VLT is a registered Danfoss trademark
34
VLT
®
5000 INTERBUS
PNU
Parameter
Factory setting
Range
Changes 4-Setup
#
description
during operation
200
Output frequency
Only clockwise,
No
Yes
range/direction
0-132 Hz
201
Output frequency low limit
0.0 Hz
0.0 - f
MAX
Yes
Yes
202
Output frequency high limit
66 / 132 Hz
f
MIN
- par. 200
Yes
Yes
203
Reference/feedback area
Min - max
Yes
Yes
204
Minimum reference
0.000
-100,000.000-Ref
MAX
Yes
Yes
205
Maximum reference
50.000
Ref
MIN
-100,000.000
Yes
Yes
206
Ramp type
Linear
Yes
Yes
207
Ramp-up time 1
Depends on unit
0.05 - 3600
Yes
Yes
208
Ramp-down time 1
Depends on unit
0.05 - 3600
Yes
Yes
209
Ramp-up time 2
Depends on unit
0.05 - 3600
Yes
Yes
210
Ramp-down time 2
Depends on unit
0.05 - 3600
Yes
Yes
211
Jog ramp time
Depends on unit
0.05 - 3600
Yes
Yes
212
Quick stop ramp-down time
Depends on unit
0.05 - 3600
Yes
Yes
213
Jog frequency
10.0 Hz
0.0 - par. 202
Yes
Yes
214
Reference function
Sum
Yes
Yes
215
Preset reference 1
0.00 %
- 100.00 - 100.00 % Yes
Yes
216
Preset reference 2
0.00 %
- 100.00 - 100.00 % Yes
Yes
217
Preset reference 3
0.00 %
- 100.00 - 100.00 % Yes
Yes
218
Preset reference 4
0.00 %
- 100.00 - 100.00 % Yes
Yes
219
Catch up/slow down value
0.00 %
0.00 - 100 %
Yes
Yes
220
221
Torque limit for motor mode
160 %
0.0 % - xxx %
Yes
Yes
222
Torque limit for regenerative operation
160 %
0.0 % - xxx %
Yes
Yes
223
Warning: Low current
0.0 A
0.0 - par. 224
Yes
Yes
224
Warning: High current
I
VLT,MAX
Par. 223 - I
VLT,MAX
Yes
Yes
225
Warning: Low frequency
0.0 Hz
0.0 - par. 226
Yes
Yes
226
Warning: High frequency
132.0 Hz
Par. 225 - par. 202
Yes
Yes
227
Warning: Low feedback
-4000.000
-100,000.000 - par. 228 Yes
228
Warning: High feedback
4000.000
Par. 227 - 100,000.000 Yes
229
Frequency bypass, bandwidth
OFF
0 - 100 %
Yes
Yes
230
Frequency bypass 1
0.0 Hz
0.0 - par. 200
Yes
Yes
231
Frequency bypass 2
0.0 Hz
0.0 - par. 200
Yes
Yes
232
Frequency bypass 3
0.0 Hz
0.0 - par. 200
Yes
Yes
233
Frequency bypass 4
0.0 Hz
0.0 - par. 200
Yes
Yes
234
Motor phase monitor
Enable
Yes
Yes
Conversion
index
0
-1
-1
0
-3
-3
0
-2
-2
-2
-2
-2
-2
-1
0
-2
-2
-2
-2
-2
-1
-1
-1
-1
-1
-1
-3
-3
0
-1
-1
-1
-1
0
Data
type
5
6
6
5
4
4
5
7
7
7
7
7
7
6
5
3
3
3
3
6
6
6
6
6
6
6
4
4
6
6
6
6
6
5
VL
T5000
parameter
list