MG.10.O1.02 – VLT is a registered Danfoss trademark

24

VLT

®

 5000 INTERBUS

Status word under VLT standard
The status word is used for informing the master
(e.g. a PC) about the condition of the slave (VLT
5000 Series).

Slave

Master

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
no.

Bit

Bit = 0

Bit = 1

00

Control not ready

Ready

01

VLT not ready

Ready

02

Coasting

Enable

03

No fault

Trip

04

Reserved

05

Reserved

06

Reserved

07

No  warning

Warning

08

Speed 

 ref.

Speed = ref.

09

Local control

Bus  control

10

Out of range

Frequency  OK

11

Not running

Running

12

VLT OK

Stalling,  autostart

13

Voltage  OK

Above limit

14

Torque  OK

Above limit

15

Timer  OK

Above limit

Bit 00, Control not ready/ready:
Bit 00 = "0" means that the frequency converter
has tripped.
Bit 00 = "1" means that the frequency converter
controls are ready, but that the power component is
not necessarily receiving any power supply (in case
of external 24 V supply to controls).

Bit 01, VLT not ready/ready:
Same meaning as bit 00; however, there is also a
supply to the mains component, and the frequency
converter is ready to run when it receives the
necessary  start  signals.

Bit 02, Coasting/enable:
Bit 02 = "0" means that the control word bit 03 is
"0" (Coasting) or that VLT 5000 Series has tripped.
Bit 02 = "1" means that control word bit 03 is "1"
and that VLT 5000 Series has not tripped.

Bit 03, No fault/trip:
Bit 03 = "0" means that VLT 5000 Series is not in a
fault condition. Bit 03 = "1" means that the VLT

Output

frequency

Status

word

Bit 10, Data not valid/valid:
Used for telling VLT 5000 whether the control word is
to be used or ignored. Bit 10 = "0" means that the
control word is ignored. Bit 10 = "1" means that the
control word is used. This function is relevant because
the control word is always contained in the telegram,
regardless of the type of telegram used, i.e. it is
possible to disconnect the control word if it is not to be
used in connection with updating or reading of
parameters.
Bit 11, Relay 01:
Bit 11 = "0": Relay 01 not activated. Bit 11 = 1:
Relay 01 activated, provided 

Control word bit

 has

been chosen in parameter 323.

Bit 12, Relay 04:
Bit 12 = "0": Relay 04 has not been activated. Bit
12 = "1": Relay 04 has been activated, provided

Control word bit

 has been chosen in parameter 326.

NB!

Unless  otherwise  mentioned,  the  control
word bit is combined (gated) with the
corresponding function on the digital inputs

as a logic "or" function.

Bits 13/14, Choice of Setup:
Bits 13 and 14 are used for choosing among the
four menu Setups in accordance with the following
table:

Setup

Bit 14

Bit 13

1

0

0

2

0

1

3

1

0

4

1

1

This function is only possible if 

Multi-Setup

 has been

selected in parameter 004.

NB!

Parameter 507 is used for choosing how bits 13/14
are to be combined (gated) with the corresponding
function on the digital inputs.

Bit 15, No function/reversing:
Reversing of the direction of rotation of the motor.
Bit 15 = "0" leads to no reversing, bit 15 = "1" leads
to  reversing.

Please note that, in the factory setting, reversing
has been chosen as digital in parameter 506, which
means that bit 15 will only lead to reversing if 

bus,

logic or

 or 

logic and

 (however, 

logic and

 only

together with terminal 19) has been selected.

FC  Pr

ofile

Summary of Contents for VLT 5000 Series

Page 1: ...mark and most other countries Danfoss A S does not warrant that a software program produced according to the guidelines provided in this manual will function properly in every physical hardware or sof...

Page 2: ...abbreviations words and phrases you must know to understand this manual This chapter also contains a complete parameter list with parameter designations default settings setting ranges etc Chapter 13...

Page 3: ...FIBUS Manual MG 10 EX YY Quick Setup MG 50 FX YY LCPremote mounting kit IP 20 MI 56 AX 51 Brake instructions MI 50 DX YY LC filter VLT 5001 5011 MI 56 DX 51 IP 20 terminal cover MI 56 CX 51 Syncron an...

Page 4: ...system provides two different types of communication Process Data and PCP Peripherals Communication Protocol The Process Data is cyclic communication to devices with high priority This type of communi...

Page 5: ...Distance Max 12 8 km Cu Segm Length Max 400 m 1200 ft between 2 nodes Cable Belden 8103 or equivalent Cable lengths number of nodes The maximum length of the Cable is only provided if the bus cable h...

Page 6: ...ering number 175Z3122 Synchronizing and positioning option INTERBUS Communication Option as above but wihtout memory option This option is intended as and INTERBUS Option to the Synchronizing and posi...

Page 7: ...the screen to ground for example by means of a cable clamp or a conductive cable gland The INTERBUS Option Card is connected to the remote bus line via MK 100A or MK 101A for the incomming INTERBUS ca...

Page 8: ...O PCP Communication running UL Power OK Green Voltage within permissable range No Voltage VLT 5000 Series is provided with different clamps and brackets to enable a proper ground connec aLso at high f...

Page 9: ...to DB9 30 mm Interbus Cable VLT5000 to VLT5000 DO DO DI DI C O M RBST RB 65 66 62 63 64 65 66 62 63 64 DO DO DI DI C O M DO DO DI DI C O M RBST 1 9 6 5 DO DO DI DI C O M 3 6 1 7 2 RB 65 66 62 63 64 D...

Page 10: ...VLT is a registered Danfoss trademark 10 VLT 5000 INTERBUS Interbus Cable VLT 5000 Bookstyle Interbus Cable VLT 5000 Compact Note Only ingoing connector set is showed Cable routing and connectors IBS...

Page 11: ...VLT 5000 INTERBUS MG 10 O1 02 VLT is a registered Danfoss trademark 11 Routing the bus Cable VLT 5060 VLT 5300 IP20 Note Only ingoing cable set is showed Cable routing and connectors...

Page 12: ...MG 10 O1 02 VLT is a registered Danfoss trademark 12 VLT 5000 INTERBUS Routing the bus Cable VLT 5060 VLT 5300 IP54 Note Only ingoing cable set is showed Cable routing and connectors...

Page 13: ...number of PCD s can be done by accesing the VLT 5000 s Parameter 807 The Parameter can be changed at any time but the changes wil first take place at the next powerup or if the Master sends out a Bus...

Page 14: ...indexes are not used and must be set to zero The 6000H 6001H Objects can have from 9 up to 37 Sub indexes depending on how many PCD words there has been assigned The drawing below shows a configurati...

Page 15: ...d In state B the statusword is equal to xx01H Drivecom 21 Profile Not ready to switch on STW xx00h Switched on 0 1 2 11 7 3 4 5 6 9 8 12 10 STW xx33h Disable Voltage xxxx xx0x or Qiuck stop xxxx x01x...

Page 16: ...n be switched off 7 READY TO SWITCH ON SWITCH ON DIS ABLED Event Quick Stop or Disable Voltage com mand Action None 8 OPERATION ENABLED READY TO SWITCH ON Event Shutdown command Action Execute the par...

Page 17: ...cy is maintained even if the reference is changed Bit 05 1 means that the frequency converter is again able to regulate and the given reference is followed Bit 06 Ramp stop start Bit06 0 The VLT contr...

Page 18: ...it 01 1 Bit 04 1 means that control word bit 01 0 Bit 05 Quick stop Run Bit 05 0 means that control word bit 02 1 Bit 05 1 means that control word bit 02 0 Bit 06 Start enable start disable Bit 06 0 s...

Page 19: ...nverter in the form of a 16 bit word The value is transmitted as a whole number 32768 to 32767 The value is handled as RPM Actual output RPM Slave Master 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no T...

Page 20: ...elta Speed unsigned 32 and index 2 is Delta Time unsigned 16 If Delta Time is set to 0 zero the ramp is disabled The VLT 5000 Interbus Option translate these two values into the VLT 5000 parameters 10...

Page 21: ...00 0200 5115 U5 supply Earth fault 0000 0400 2240 earth leakage Overcurrent 0000 0800 2310 continuous over current Torque limit 0000 1000 8311 excess torque Motor thermistor 0000 2000 4310 excess temp...

Page 22: ...r PCP communication All parameters in the VLT 5000 are mapped to the Danfoss specific objects starting from object 22000D 55F0H The first object is 22001D which corresponds to read VLT 5000 parameter...

Page 23: ...ined gated with the corresponding function in the digital inputs Bit 04 Quick stop ramp Quick stop which uses the ramp time in parameter 212 Bit 04 0 leads to a quick stop Bit 04 1 means that the freq...

Page 24: ...not valid valid Used for telling VLT 5000 whether the control word is to be used or ignored Bit 10 0 means that the control word is ignored Bit 10 1 means that the control word is used This function...

Page 25: ...ans that the inverter has stopped because of over temperature but that the unit has not tripped and will continue once the overtemperature stops Bit 13 Voltage OK above limit Bit 13 0 means that the v...

Page 26: ...ontrol without INTERBUS 6 NO COM OPT CONTROL Select setup 4 SELECT SETUP 4 7 Function The time out counter is triggered at the first reception of a valid control word When process data is used Acyclic...

Page 27: ...PQ 2 i e subindex 1 PCD 3 subindex 2 PCD 3 and so on Each subindex can hold the number of any of the VLT parameters Parameters 916 PCD config read PCD IN RD Selections Sub index 1 1 000 Parameter Sub...

Page 28: ...nal SW error MSB Bit 12 15 describes the Internal option error code 971 Store data values STORE DATA VALUE Selections No action NO ACTION 0 Store active setup STORE ACTIVE SETUP 1 Store all setups STO...

Page 29: ...f all the VLT parameters that have been changed from factory setting Each of the three parameters can be read as an array by means of the acyclical PCP read service The subindexes start at 1 and follo...

Page 30: ...msec Status word Actual speed 2 msec Parameter read via PCD part 2 msec Parameter write via PCD1 2 83 msec Parameter write via PCD3 4 165 msec Parameter write via PCD5 7 325 msec Parameter read via PC...

Page 31: ...been alleviated and the master has acknowledged the alarm message by setting bit 7 in the Control word can the VLT resume operation Any warning within the VLT is represented by a single bit within a...

Page 32: ...tput ISO International Standards Organization LSB Least Significant Bit MSB Most Significant Bit MAV HIW Main Actual Value MRV HSW Main Reference Value OD OV Object Directory PI PE Peripherial input P...

Page 33: ...18 500 kW No Yes 1 6 103 Motor voltage Depends on the unit 200 500 V No Yes 0 6 104 Motor frequency 50 60 Hz No Yes 0 6 105 Motor current Depends on the unit 0 01 IVLT MAX No Yes 2 7 106 Rated motor...

Page 34: ...00 100 00 100 00 Yes Yes 216 Preset reference 2 0 00 100 00 100 00 Yes Yes 217 Preset reference 3 0 00 100 00 100 00 Yes Yes 218 Preset reference 4 0 00 100 00 100 00 Yes Yes 219 Catch up slow down v...

Page 35: ...Yes 323 Relay 01 output Ready no thermal warning Yes Yes 324 Relay 01 ON delay 0 00 sec 0 00 600 sec Yes Yes 325 Relay 01 OFF delay 0 00 sec 0 00 600 sec Yes Yes 326 Relay 04 output Ready remote contr...

Page 36: ...Yes Yes 423 U 1 voltage parameter 103 0 0 UVLT MAX Yes Yes 424 F 1 frequency parameter 104 0 0 parameter 426 Yes Yes 425 U 2 voltage parameter 103 0 0 UVLT MAX Yes Yes 426 F 2 frequency parameter 104...

Page 37: ...No 521 Data read out Torque No No 522 Data read out Power kW No No 523 Data read out Power HP No No 524 Data read out Motor voltage No No 525 Data read out DC link voltage No No 526 Data read out Mot...

Page 38: ...et Yes No 620 Operating mode Normal function Normal function No No 621 Nameplate VLT type No No 622 Nameplate Power section No No 623 Nameplate VLT ordering number No No 624 Nameplate Software version...

Reviews: