Description of choice:
,
, and
show when
the motor has stopped and when the frequency converter
has a start command when each of the following is
selected:
•
[0] Digital input
,
•
[1] Serial port
,
•
[2] Logic and
or
[3] Logic or
.
Dig. input
Ser. port
Function
0
0
Stop
0
1
Stop
1
0
Start
1
1
Start
Table 4.30 Function Description for
[0] Digital input
Dig. input
Ser. port
Function
0
0
Stop
0
1
Start
1
0
Stop
1
1
Start
Table 4.31 Function Description for
[1] Serial port
Dig. input
Ser. port
Function
0
0
Stop
0
1
Stop
1
0
Stop
1
1
Start
Table 4.32 Function Description for
[2] Logic and
Dig. input
Ser. port
Function
0
0
Stop
0
1
Start
1
0
Start
1
1
Start
Table 4.33 Function Description for
[3] Logic or
506
Reversing
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See function description for
parameter 502 Coasting stop.
Description of choice:
,
, and
show when
the motor is running clockwise and anti-clockwise when
each of the following is selected:
•
[0] Digital input
,
•
[1] Serial port
,
•
[2] Logic and
or
[3] Logic or
.
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Clockwise
1
0
Anti-clockwise
1
1
Anti-clockwise
Table 4.34 Function Description for
[0] Digital input
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Anti-clockwise
1
0
Clockwise
1
1
Anti-clockwise
Table 4.35 Function Description for
[1] Serial port
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Clockwise
1
0
Clockwise
1
1
Anti-clockwise
Table 4.36 Function Description for
[2] Logic and
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Anti-clockwise
1
0
Anti-clockwise
1
1
Anti-clockwise
Table 4.37 Function Description for
[3] Logic or
507
Selection of Setup
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See function description of
parameter 502 Coasting stop.
Description of choice:
, and
show
which Set-up (parameter
004 Active Setup
) is selected for
each of the following:
•
[0] Digital input
,
•
[1] Serial communication
,
•
[2] Logic and
or
[3] Logic or
.
Programming
Design Guide
118
Danfoss A/S © Rev. May/2014 All rights reserved.
MG27E402
4
4