Maximum cable length (unscreened/
unarmoured)
1)
200 m
Maximum cable length (screened/armoured)
1)
100 m
Enclosure
IP20
Maximum rated current
1)
16 A
Maximum voltage
1)
480 V AC
Minimum distance between frequency
converter and motor coil
Side-by-side
Minimum distance above and below motor
coil
100 mm
Mounting
Vertical mounting
only
Dimensions HxWxD (mm)
2)
200x90x152
Weight
3.8 kg
Table 1.4 Technical Data for VLT 2803-2875 Motor Coils
1) Parameter 411 Switching frequency=4500 Hz.
2) For mechanical dimensions see chapter 3.1.1 Overview.
For ordering numbers for motor coil module, see
chapter 1.10 Accessories for VLT 2800
1.7.10 RFI 1B Filter
All frequency converters cause electromagnetic noise in
the mains supply when they are operating. An RFI (radio
frequency interference) filter reduces the electromagnetic
noise in the mains supply. Without an RFI filter, there is a
risk that a frequency converter disrupts other electrical
components that are connected to the mains and might
thus cause operating disruption. By fitting an RFI 1B filter
module between the mains supply and the VLT 2800, the
VLT 2800 complies with the EMC norm EN 55011-1B.
To comply with EN 55011-1B, the RFI 1B filter module must
be fitted together with a VLT 2800 with integral 1A RFI
filter.
Illustration 1.3 RFI 1B Filter Example
Maximum cable length (screened/armoured)
200-240 V
100 m (At 1A: 100
m)
Maximum cable length (screened/armoured)
380-480 V
25 m (At 1A: 50
m)
Enclosure
IP20
Maximum rated current
16 A
Maximum Voltage
480 V AC
Maximum voltage to ground
300 V AC
Minimum distance between VLT and RFI 1B
filter
Side-by-side
Minimum distance above and below RFI 1B
filter
100 mm
Mounting
Vertical mounting
only
Dimensions HxWxD (mm)
200x60x87
Weight
0.9 kg
Table 1.5 Technical Data for VLT 2803–2875 RFI 1B Filter
For ordering number for RFI 1B filter module, see
chapter 1.10 Accessories for VLT 2800
Introduction to VLT 2800
Design Guide
12
Danfoss A/S © Rev. May/2014 All rights reserved.
MG27E402