Technical item or function
Technical data
Ambient conditions
Ambient operating tempera-
ture
FR4-FR9 I
L
current:
-10 °C (-14 °F) (no frost)...+40 °C (104 °F)
I
H
current: -10 °C (-14 °F) (no frost)...+50 °C (122 °F)
FR10-FR11 (IP21/UL Type 1)
I
H
/I
L
: –10 °C (-14 °F) (no frost)…+40 °C (104 °F) (except 525–690 V, 0461
and 0590: –10 °C (-14 °F) (no frost)… +35 °C (95 °F))
FR10 (IP54/UL Type 12)
I
H
/I
L
: –10 °C (-14 °F) (no frost)…+40 °C (104 °F) (except 380–500 V,
0520 V and 525–690 V, 0416: –10 °C (-14 °F) (no frost)…+35 °C (95 °F))
For higher ambient temperatures see Motor connection – Continuous
output current in this table.
Storage temperature
-40 °C (-104 °F)...+70 °C (158 °F)
Relative humidity
0–95% RH, non-condensing, non-corrosive, no dripping water
Air quality:
•
chemical vapors
•
mechanical particles
Designed according to
•
IEC 60721-3-3, AC drive in operation, class 3C2
•
IEC 60721-3-3, AC drive in operation, class 3S2
Altitude
100% load capacity (no derating) up to 1000 m (3281 ft) 1% derating for
each 100 m (328 ft) above 1000 m (3281 ft)
Maximum altitudes:
•
FR4-8 208–240 V: 3000 m (9843 ft) (TN, TT, and IT systems)
•
FR9-11 208–240 V: 4000 m (13123 ft) (TN, TT, and IT systems)
•
208–240 V: 3000 m (9843 ft) (corner-grounded network*)
•
FR4-8 380–500 V: 3000 m (9843 ft) (TN, TT, and IT systems)
•
FR9-11 380–500 V: 4000 m (13123 ft) (TN, TT, and IT systems)
•
380–500 V: 2000 m (6562 ft) (corner-grounded network **)
•
525–690 V: 2000 m (6562 ft) (TN, TT and IT systems, no corner-
grounding)
* Corner-grounded network is permitted for FR4-FR9 (Main voltage
208–240 V) up to 3000 m (see
6.2.1 Installation in a Corner-grounded
** Corner-grounded network is permitted for FR9 – FR11 (Main voltage
380–500 V) up to 2000 m (see
6.2.1 Installation in a Corner-grounded
Vibration
IEC/EN 60068-2-6
IEC/EN 61800-5-1
5–150 Hz
Displacement amplitude 1 mm (peak) at 5-15.8 Hz (FR4-FR9)
Maximum acceleration amplitude 1 G at 15.8–150 Hz (FR4-FR9)
Displacement amplitude 0.25 mm (peak) at 5–31 Hz (FR10–FR11)
Maximum acceleration amplitude 0.25 G at 31–150 Hz (FR10–FR11)
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G
156 | Danfoss A/S ©