12.7.7 Power Ratings for Mains Voltage 525–690 V (UL Rating 600 V), North America
Table 50: Power Ratings in Mains 525–600 V, 60 Hz, 3~
Enclosure
size
Drive
type
Input
current
I
in
(1)
Low
loadabili-
ty: I
L
[A]
(2)
Low
loadabili-
ty: 10%
overload
I [A]
High
loadabili-
ty: I
H
[A]
(2)
High
loadabili-
ty: 50%
overload
I [A]
Loadabili-
ty: Max I
S
2 s
Motor
shaft
power
(3)
:
10% over-
load
104°F [hp]
Motor
shaft
power
(3)
:
50% over-
load
122°F [hp]
FR6
0004
4.5
4.5
5.0
3.2
4.8
6.4
3
2
0005
5.5
5.5
6.1
4.5
6.8
9.0
4
3
0007
7.5
7.5
8.3
5.5
8.3
11.0
5
4
0010
10.0
10.0
11.0
7.5
11.3
15.0
7.5
5
0013
13.5
13.5
14.9
10.0
15.0
20.0
10
7.5
0018
18.0
18
19.8
13.5
20.3
27.0
15
10
0022
22.0
22.0
24.2
18.0
27.0
36.0
20
15
0027
27.0
27.0
29.7
22.0
33.0
44.0
25
20
0034
34.0
34.0
37.0
27.0
41.0
54.0
30
25
FR7
0041
41.0
41.0
45.0
34.0
51.0
68.0
40
30
0052
52.0
52.0
57.0
41.0
62.0
82.0
50
40
FR8
0062
62.0
62.0
68.0
52.0
78.0
104.0
60
50
0080
80.0
80.0
88.0
62.0
93.0
124.0
75
60
0100
100.0
100.0
110.0
80.0
120.0
160.0
100
75
FR9
0125
125.0
125.0
138.0
100.0
150.0
200.0
125
100
0144
144.0
144.0
158.0
125.0
188.0
250.0
150
125
0170
170.0
170.0
187.0
144.0
216.0
288.0
150
150
0208
208.0
208.0
229.0
170.0
255.0
340.0
200
150
FR10
(3)
0261
261.0
261.0
287.0
208.0
312.0
416.0
250
200
0325
325.0
325.0
358.0
261.0
392.0
522.0
350
250
0385
385.0
385.0
424.0
325.0
488.0
650.0
400
350
0416
416.0
416.0
358.0
325.0
488.0
650.0
450
350
FR11
(3)
0460
460.0
460.0
506.0
385.0
578.0
770.0
500
450
0502
502.0
502.0
552.0
460.0
690.0
920.0
550
500
0590
590.0
590.0
649.0
502.0
753.0
1004.0
600
550
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See
3
575 V
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G
| 153
Danfoss A/S ©
2018.06