12.7.4 Power Ratings for Mains Voltage 380–500 V
Table 47: Power Ratings in Mains 380–500 V, 50 Hz, 3~
Enclosure
size
Drive
type
Input
current
I
in
(1)
Low load-
ability: I
L
[A]
(2)
Low load-
ability:
10%
overload
I [A]
High
loadabili-
ty: I
H
[A]
(2)
High
loadabili-
ty: 50%
overload
I [A]
Loadabili-
ty: Max I
S
2 s
Motor
shaft
power
(3)
:
10% over-
load 40°C
[kW]
Motor
shaft
power
(3)
:
50% over-
load 50°C
[kW]
FR4
0003
3.3
3.3
3.6
2.2
3.3
4.4
1.1
0.75
0004
4.3
4.3
4.7
3.3
5
6.6
1.5
1.1
0005
5.6
5.6
6.2
4.3
6.5
8.6
2.2
1.5
0007
7.6
7.6
8.4
5.6
8.4
11.2
3
2.2
0009
9
9
9.9
7.6
11.4
15.2
4
3
0012
12
12
13.2
9
13.5
18
5.5
4
FR5
0016
16
16
17.6
12
18
24
7.5
5.5
0022
23
23
25.3
16
24
32
11
7.5
0031
31
31
34
23
35
44
15
11
FR6
0038
38
38
42
31
47
62
18.5
15
0045
46
46
49.5
38
57
76
22
18.5
0061
61
61
67
46
69
92
30
22
FR7
0072
72
72
79
61
92
122
37
30
0087
87
87
96
72
108
144
45
37
0105
105
105
116
87
131
174
55
45
FR8
0140
140
140
154
105
158
210
75
55
0168
170
170
187
140
210
280
90
75
0205
205
205
226
170
255
340
110
90
FR9
0261
261
261
287.1
205
308
410
132
110
0300
300
300
330
245
368
490
160
132
FR10
(3)
0385
385
385
424
300
450
600
200
160
0460
460
460
506
385
578
770
250
200
0520
520
520
576
460
690
920
250
250
FR11
(3)
0590
590
590
649
520
780
1040
315
250
0650
650
650
715
590
885
1180
355
315
0730
730
730
803
650
975
1300
400
355
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See
3
400 V
Specifications