4

Insert for cover of WB12 Wiring
Centre.  Cut-out and place over
pillars in cover.

$

Commissioning

12.

Lower the front flap and remove the anti-discharge paper strip
from between the batteries and their contacts, and ensure the
mains power to the control circuit is switched on.

13.

Press and release the recessed RESET button to ensure the
factory pre-set programme is active.

14.

Establish with the customer the requirements for the operating
mode, and adjust as follows:

Clock type - 24 hour or 12 hour with AM/PM indication.

The factory pre-set is 24 hour. To convert to 12 hour, press
and hold down the NEXT and DAY buttons until the display
changes, then release. (Repeat to return to a 24 hour clock.)

Temperature display - °C or °F

The factory pre-set is °C. To convert to display all
temperatures in °F, press and hold down the DAY and
COPY buttons until the display changes. (Repeat to return
to a °C display.)

15.

Check the existing space temperature by pressing and holding
down the two buttons: NEXT and COPY, until the display
changes from time to temperature.

16a. If the set temperature is below the space temperature, use the

s

 button to raise the set temperature.  The flame symbol will

appear in the display.  Check that the heating plant operates
correctly.

16b. If the set temperature is above the space temperature, use the

t

 button to lower the set temperature below the space

temperature.  The flame symbol will disappear.  Check that the
heating plant does not operate.

17.

These models are supplied with a factory pre-set programme
which will be active after a RESET has been performed. The pre-
set programme is shown in the chart with the Setting Instructions.
The chart also has spaces for users own times and temperatures
as required by them.

18.

The time and programme memory are maintained by the batteries
which should last more than two years.  Every 24 months the
batteries should be renewed.  Internal circuitry retains the time
and programme memory for one minute, long enough for the
batteries to be changed.

If the batteries volts drop, before a change is due, a battery
symbol will blink in the display.  When this occurs the TP75 will
operate normally for 2 weeks.  After the 15th midnight all relays
will switch to OFF, the unit will shut down with just the time
shown.  When new batteries are fitted the unit will start to operate
normally again.

Advise the User to enter their own times and temperatures in the
chart on the Setting Instructions.

Post-commissioning

Optimum Start Control

If this has been enabled, initially set to the recommended 30 minutes
start-up duration and the event 1 temperature is not achieved by the
event 1 time, then refer to the Setting Instructions and increase the
start-up duration one stage, i.e. to 1 hour.
If  the  space  temperature  at  the  beginning  of  an  Optimum  Start
sequence  is  consistently  lower  than  the  programmed  event  1
temperature by more that 4°C, then the event 1 temperature may not
be achieved by the event 1 time. In this case the event 1 time should
be brought forward sufficiently to compensate, so that the comfort
temperature is achieved when actually required.

Intelligent Anticipator

If, when the heating equipment is switched on, the room temperature
is 2°C or more lower than the programmed temperature the electronic
anticipation function measures the rate of rise in the sensed temperature
and will switch the heating plant off before the programmed temperature
is reached. The residual heat in the system after the heating plant has
shut down will ensure that the comfort temperature is achieved. This
will improve the comfort conditions and minimise fuel consumption.

Part No. 8958  Iss 8  12/01

Danfoss Randall Limited

Ampthill Road
Bedford, MK42 9ER
Tel: (01234) 364621  Fax: (01234) 219705
Email: [email protected]
Website: www.danfoss-randall.co.uk

Danfoss Randall can accept no responsibility for possible errors in catalogues, brochures and other printed material, and reserves the right
to alter its products without notice.  This also applies to products already on order provided that such alterations can be made without
subsequent changes being necessary in specifications already agreed.

HEATPLAN 

SYSTEM

TS2

Remote

Sensor

if Fitted

TP75

Remote Devices

COM

On Off

A

B C

1

2

3

4

5

6

2

9

TS75 or TS15

Off

On

N L

1

2

3 4

6 10

11

11

12

5

ATC

COM

N

/

C

N

/

O

CALL

SAT

1

2

3

1

2

3

4

5

6

7

8

9

10

11

12

N

L

N

L

MAINS

FUSED

3A

1

2

3

WIRING CONNECTIONS FOR

TP75 WITH A TS75 HSP or TS15 HSP

Heatplan Control Pack

4

5

6

7

PERM. 

L

SW. 

L

N

BOILER

PUMP

IF 

REQUIRED

BLUE

BROWN

GREY

ORANGE

1

9

10

8

HEATPLAN

ACTUATOR

HTG

IF BOILER DOES NOT HAVE PUMP TERMINALS, CONNECT PUMP TO 7

(L), 6 (N) & 5 (   ) ON WB12.

BLUE

BROWN

GREY

ORANGE

1

12 10

8

HEATPLAN

ACTUATOR

DHW