background image

2

Fig. 4 Factory pre-set

DIL switch
settings.

7 day

OSC OFF

ON/OFF

Chrono 3

5/2 day

OSC ON

CHRONO

Chrono 6

TP75 Installation

The  unit  (and  remote  sensor  when  used)  must  be  installed  by  a
competent  electrician  and  the  installation  should  conform  to  IEE
Wiring Regulations.
The electronics and relay switching circuits are powered by two AA
size  alkaline  batteries,  however  mains  electricity  control  circuits
connected to this unit should be wired through a full disconnect in
accordance with BS EN60730-1, i.e. one which provides an air gap of
at  least  3mm  in  both  poles  of  the  mains,  e.g.  a  13amp  plug  and
unswitched socket, or a switched, fused outlet with neon; either fitted
with a 2 amp (max.) fuse.

Fixing

Fig. 2 TP75 or TS2 location

1a.

TP75

Select the desired fixing position. (This should

adhere to normal room thermostat practice, see Fig. 2).

1b.

TP75A

Select the desired fixing position for the TS2

remote sensor. (This should adhere to normal room thermostat
practice, see Fig. 2). Select the desired fixing position for the
TP75A. 1·0mm² solid copper cable should be used to connect
the TP2 to the TP75A.  Note that

a)

the cable length should not exceed 50 metres,

b)

to avoid electrical interference the cable should not be run
parallel in close proximity to other cables carrying mains
electricity, and where necessary the cable should cross
over mains cabling at right angles.

Fig. 3

   Wallplate fixing clearances.

2.

When fixing the heating controller wallplate note that the terminals
are at the top and the vertical centre line of the heating controller
is at the right hand edge of the terminal 4 recess.  Observe the
clearance required for fitting and removal,  Fig. 3.

3.

Fix the wallplate to the wall or plaster box as required.

4.

Make the wiring connections for the system control circuits, (and
remote sensor when used).

5.

Surface cables can only enter from below the unit. If mounted on
a plaster box cables can enter from the rear through the aperture
in the wallplate.

6.

These models do not require an earth connection. However, an
earth terminal is provided on the wallplate to ensure earth
continuity for the connections to the heating plant. (A neutral
looping terminal is also provided.)

7.

The diagrams on the next page show typical wiring circuit's with
which the units may be used, together with terminal to terminal
wiring information for use with the WB12 Wiring Box included
with Heatshare and Heatplan Control Packs.

8.

Clear all dust and debris from the area.

9.

Before fixing the unit on to its wallplate, ensure that the four DIL
switches on the rear of the unit (see Fig. 4)  have been moved to
the required settings; the choices are:-

Switch No. 1- 5/2 DAY or 7 DAY.

When  the  switch  is  in  the  7  DAY  position  each  day  may  be

programmed with different switching  times and temperatures.

Placing the switch in the 5/2 DAY position enables Monday to

Friday to be programmed with one set of switching  times and

temperatures, and Saturday and Sunday to be programmed with

a different set.

Switch No. 2 - OSC ON or OSC OFF

This is used to enable or disable the optimum start control (OSC)

function  for  event  1.  To  cater  for  different  types  of  building

construction with differing fabric constants there are four start-

up  curves  from  which  to  choose,  (see  the  diagram  over  the

page). These curves dictate how long before event 1 the heating

equipment will be switched on. The selectable start-up durations

are  0:00,  0:30,  1:00,  1:30  or  2:00  (2  hours).  (Selecting  0

effectively disables the function).
Once initiated the difference between the space temperature

and  the  event  1  temperature  is  used  to  generate  a  pre-heat

period proportional to the OSC period selected. The closer the

space temperature is to the event 1 temperature, the shorter the

pre-heat period. Refer to the earlier section on Optimum Start

Control for more detail.
It  is  recommended  that  the  initial  setting  of  the  OSC  is  30

minutes. See the section on post-commissioning.

Switch No. 3 - CHRONO or ON/OFF

With this switch set to ON/OFF the TP75 will act as a conventional

room  thermostat,  switching  the  heating  plant  to  maintain  the

programmed temperature. When set to CHRONO the control

function selected by switch No. 4 is enabled.

IMPORTANT

. For systems with motorised zone valves ON/OFF

mode is recommended.

Switch No. 4 - Chrono 6 or Chrono 3

This  switch  configures  the  TP75  to  control  different  forms  of

heating system, typically as follows:
Use  Chrono  3  for  high  thermal  inertia  systems,  e.g.  floor

standing cast iron boilers.
Use Chrono 6 for low thermal inertia systems, e.g. low water

content boilers and combi. boilers.
See the earlier section on Chrono-proportional Control for more

detail.

10.

Position the slots in the top surface of the module over the lugs
at the top of the wallplate, and hinge downwards until the module
is pressed fully against the wallplate. Tighten the two screws
from below to fix the module to the wallplate.

11.

Before setting the programmes the unit and circuits should be
checked. Refer to the following Commissioning Instructions.

30mm

minimum

Wall or Plaster box

mounting holes

Aperture for rear

cable entry

Knockouts for

bottom cable

entry

Outline of unit

Terminals

C/L

N &

looping

terminals

Clearance  for

screwdriver

access

Reviews: