4 How to Configure the System
4.1 Configuring BACnet
4.1.1 Initialization Procedure
Parameter
Default Value
Setting for BACnet
Digital and control word
Digital and control word
8-02 Control Source
FC RS485
FC RS-485
8-03 Control Timeout Time
60 sec
1)
Off
1)
Resume setup
1)
Do not reset
1)
Disable
n.a.
8-09 Communication Charset
ANSI X3.4
8-10 Control Profile
FC Profile
2)
Table 4.1 General Settings
Parameter
Default Value
Setting for BACnet
8-30 Protocol
FC
BACnet
8-31 Address
1
1
3
8-32 Baud Rate
9600
9600 baud
10ms
10ms
5000ms
5000ms
Table 4.2 FC Port Settings
1
) Depending on your application.
2)
Depending on the BMS system
3)
The adress setting is depending on the system and each device connected to the BACnet MS/TP must have a unique adress on
this MS/TP network. Please also see section
Parameter Overview >Parameter List
.
Parameter
Default Value
Setting for BACnet
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Table 4.3 Digital/Bus Settings
Name
Default Value
Setting for BACnet
8-70 BACnet Device Instance
1
1
1
8-72 MS/TP Max Masters
127
Dependent on the Number of Masters in the system
At power up
At power up
8-75 Initialisation Password
“admin”
“admin”
Table 4.4 BACnet Settings
1
) The device instance setting is depending on the system, and each device connected to the BACnet MS/TP must have a unique
device instance in the complete system.
How to Configure the System
VLT
®
HVAC Drive Native BACnet Operating Instructions
MG.14.C1.02 - VLT
®
is a registered Danfoss trademark
11
4